AS/NZS 5000.1 0.6/1kV XLPE PVC Orange Circ Multi Core Armoured Cable

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

The 0.6/1kV Orange Circ Multi Core Armoured Cable has a rated voltage of 0.6/1kV and can be fixedly placed as a power transmission and distribution line.
Although Orange Circ XLPE Insulated PVC Sheathed cables are installed in doors, pipes, and tunnels, they are unable to withstand pressure and stress.

Performance

Electrical performance U0/U:
0.6/1kV

Chemical performance:
chemical, UV&oil resistance

Mechanical performance:
minimum bending radius:15 x overall diameter

Terminal performance:
-Maximum service temperature: 90℃
-Maximum short-circuit temperature: 250℃(Max.5s)
-Minimum service temperature: -10℃

Construction

Conductor:
Plain annealed copper conductor

Insulation:
XLPE

Laying up:
Non-hygroscopic filler

Bedding:
Polyvinylchloride compound PVC 5V-90

Bedding color:
Black

Armour:
SWA

Outer Sheath:
Polyvinyl chloride compound 5V-90

Core Identification:
2C + E - Red, Black, Green/yellow
3C + E – Red, White, Blue, Green/yellow
4C + E - Red, White, Blue, black, Green/yellow

Sheath Colour:
Orange

0-6-1kV-Multicore-XLPE-Insulated-PVC-Sheathed-Armored-Cables-(2)

1.Copper Conductor
2.XLPE Insulation
3.Laying Up

4.Bedding
5.SWA Armour
6.PVC Sheath

Cable Marking and Packing Materials

Cable Marking:
printing, embossing ,engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Specifications

-AS/NZS 5000.1 Standard
-AS/NZS 3008 Standard
-AS/NZS 1125 Standard
-SAA-173128-EA Standard

AS/NZS 5000.1 0.6/1kV 2C+E XLPE Insulated PVC Sheathed Armored Cables Specification

NOM. CONDUCTOR AREA CONDUCTOR NOM. INSULATION THICKNESS NOM. EARTH CONDUCTOR AREA NOM. EARTH CONDUCTOR INSULATION THICKNESS NOM. DIAMETER OVER BEDDING ARMOUR DIAMETER NOM. OVERALL DIAMETER APPROX. MASS
MM2 NO./ OD MM MM2 MM MM MM MM KG/KM
16 7/1.70 0.7 6 0.7 15.3 1.25 21.6 1100
25 7/2.14 0.9 6 0.7 19.2 1.25 25.8 1310
35 7/2.65 0.9 10 0.7 21.3 1.6 26.8 1765
50 19/1.89 1 16 0.7 24.1 1.6 29.7 2185
70 19/2.24 1.1 25 0.9 28.2 1.6 33.6 2745
95 19/2.65 1.1 25 0.9 31.7 2 37.7 3650
120 19/2.94 1.2 35 0.9 35.4 2 41.8 4600

AS/NZS 5000.1 0.6/1kV 2C+E XLPE Insulated PVC Sheathed Armored Cables Electrical Performance

CONDUCTOR CURRENT RATINGS ELECTRICAL CHARACTERISTICS
NOMINAL AREA UNENCLOSED  IN AIR BURIED DIRECT BURIED IN DUCTS MAXIMUM DC RESISTANCE @20°C MAXIMUM AC RESISTANCE @90℃ REACTANCE THREE PHASE VOLTAGE DROP @90℃
MM2 A  A A OHM/KM OHM/KM OHM/KM MV/AM
16 97 130 100 1.15 1.47 0.0805 2.95
25 130 170 130 0.727 0.927 0.0808 1.86
35 160 205 160 0.524 0.669 0.0786 1.35
50 195 245 190 0.387 0.494 0.0751 1
70 250 300 235 0.268 0.343 0.0741 0.703
95 310 360 285 0.193 0.248 0.0725 0.52
120 360 410 325 0.153 0.197 0.0713 0.423

AS/NZS 5000.1 0.6/1kV 3C+E XLPE Insulated PVC Sheathed Armored Cables Specification

NOM. CONDUCTOR AREA CONDUCTOR NOM. INSULATION THICKNESS NOM. EARTH CONDUCTOR AREA NOM. EARTH CONDUCTOR INSULATION THICKNESS NOM. DIAMETER OVER BEDDING ARMOUR DIAMETER NOM. OVERALL DIAMETER APPROX. MASS
MM2 NO./ OD MM MM2 MM MM MM MM KG/KM
16 7/1.70 0.7 6 0.7 17.5 1.25 22.8 1285
25 7/2.14 0.9 6 0.7 22.2 1.6 26.7 1845
35 7/2.65 0.9 10 0.7 23.5 1.6 28.7 2315
50 19/1.89 1 16 0.7 26.7 1.6 32 2935
70 19/2.24 1.1 25 0.9 31.7 2 38.3 3880
95 19/2.65 1.1 25 0.9 25.6 2 43.1 5250
120 19/2.94 1.2 35 0.9 39.9 2 45.4 5765
150 19/3.28 1.4 50 1 41.1 2.5 51.4 7560
185 37/2.65 1.6 70 1.1 46.1 2.5 56.6 9220
240 37/2.94 1.7 95 1.1 52.4 2.5 63.3 11740

AS/NZS 5000.1 0.6/1kV 3C+E XLPE Insulated PVC Sheathed Armored Cables Electrical Performance

CONDUCTOR CURRENT RATINGS ELECTRICAL CHARACTERISTICS
NOMINAL AREA UNENCLOSED  IN AIR BURIED DIRECT BURIED IN DUCTS MAXIMUM DC RESISTANCE @20°C MAXIMUM AC RESISTANCE @90℃ REACTANCE THREE PHASE VOLTAGE DROP @90℃
MM2 A  A A OHM/KM OHM/KM OHM/KM MV/AM
16 83 110 83 1.15 1.47 0.0805 2.55
25 110 145 110 0.727 0.927 0.0808 1.61
35 135 170 135 0.524 0.669 0.0786 1.17
50 170 205 160 0.387 0.494 0.0751 0.868
70 215 250 200 0.268 0.343 0.0741 0.609
95 265 300 240 0.193 0.248 0.0725 0.45
120 305 345 275 0.153 0.197 0.0713 0.366
150 350 385 310 0.124 0.16 0.0718 0.307
185 405 435 355 0.0991 0.129 0.072 0.259
240 480 500 420 0.0754 0.0998 0.0709 0.216

AS/NZS 5000.1 0.6/1kV 4C+E XLPE Insulated PVC Sheathed Armored Cables Specification

NOM. CONDUCTOR AREA CONDUCTOR NOM. INSULATION THICKNESS NOM. EARTH CONDUCTOR AREA NOM. EARTH CONDUCTOR INSULATION THICKNESS NOM. DIAMETER OVER BEDDING ARMOUR DIAMETER NOM. OVERALL DIAMETER APPROX. MASS
MM2 NO./ OD MM MM2 MM MM MM MM KG/KM
16 7/1.70 0.7 6 0.7 19.4 1.6 26.3 1725
25 7/2.14 0.9 6 0.7 22.7 1.6 29.6 2335
35 7/2.65 0.9 10 0.7 24.4 1.6 31.5 2605
50 19/1.89 1 16 0.7 27.8 2 36.5 3860
70 19/2.24 1.1 25 0.9 33.4 2 41.8 5135
95 19/2.65 1.1 25 0.9 36.9 2.5 45.8 5900
120 19/2.94 1.2 35 0.9 38.1 2.5 51.7 9090
150 19/3.28 1.4 50 1 42.2 2.5 56.9 10410
185 37/2.65 1.6 70 1.1 52.2 2.5 63.1 11600
240 37/2.94 1.7 95 1.1 58.8 2.5 70.1 14700

AS/NZS 5000.1 0.6/1kV 4C+E XLPE Insulated PVC Sheathed Armored Cables Electrical Performance

CONDUCTOR CURRENT RATINGS ELECTRICAL CHARACTERISTICS
NOMINAL AREA UNENCLOSED  IN AIR BURIED DIRECT BURIED IN DUCTS MAXIMUM DC RESISTANCE @20°C MAXIMUM AC RESISTANCE @90℃ REACTANCE THREE PHASE VOLTAGE DROP @90℃
MM2 A  A A OHM/KM OHM/KM OHM/KM MV/AM
16 83 110 83 1.15 1.47 0.0805 2.55
25 110 145 110 0.727 0.927 0.0808 1.61
35 135 170 135 0.524 0.669 0.0786 1.17
50 170 205 160 0.387 0.494 0.0751 0.868
70 215 250 200 0.268 0.343 0.0741 0.609
95 265 300 240 0.193 0.248 0.0725 0.45
120 305 345 275 0.153 0.197 0.0713 0.366
150 350 385 310 0.124 0.16 0.0718 0.307
185 405 435 355 0.0991 0.129 0.072 0.259
240 480 500 420 0.0754 0.0998 0.0709 0.216