BS 6622 6.35/11kV XLPE Insulated Armoured Cable

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

Power cables for power networks, underground and in cable ducting. Suitable for direct burial.

Performance

Electrical performance U0/U:
6.35/11 (12)kV

Test Voltage (AC) :
12kV(CU)

Mechanical performance:
minimum bending radius:
Single core: 15x overall diameter
Multi core: 12 x overall diameter
(Single core 12 x overall diameter and 3 core 10 x overall diameter where bends
are positioned adjacent to a joint or termination provided that the bending is
carefully controlled by the use of a former)

Terminal performance:
-Maximum service temperature:90℃
-Maximum short-circuit temperature: 250℃(Max.5s)
-Minimum service temperature:-10℃

Fire performance:
-Flame Retardant according to IEC/EN 60332-1-2 Standard

Copper Armoured Cable Constructions

Conductor:
Class 2 Copper or Aluminium Conductors to BS EN60228

Conductor Screen:
Semi-conductive XLPE (Cross-Linked Polyethylene)

Insulation:
XLPE (Cross-Linked Polyethylene)

Insulation Screen:
Semi-conductive XLPE (Cross-Linked Polyethylene)

Metallic Screen:
Concentric copper wires or copper tape

Separator :
Binding tape

Inner Sheath:
PVC (Polyvinyl Chloride)

Armour:
Single core: AWA (Aluminium Wire)
Multi core: SWA (Galvanised steel wire)

Sheath:
PVC (Polyvinyl Chloride) or PE

Sheath Colour:
1 Core Black; 3 Core Brown, Black & Grey

BS 6622 6.3511kV XLPE Insulated Armoured Cable (2)

1. Conductor
2. Conductor Screen
3. Insulation
4. Insulation Screen
5. Filler
6. Binding Tape

7. Metallic Screen
8. Binding Tape
9. Inner Sheath
10. Armour
11. Outer Sheath

Cable Marking and Packing Materials

Cable Marking:
printing, embossing ,engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Specifications

- BS 6622, IEC/EN 60228, IEC 60502-2 Standard
- BS EN / IEC 60332-1 Flame Propagation

Single Core – Class 2 Copper Conductor, XLPE Insulated, Copper Taped Screen, PVC (PE) Sheathed

Nominal Area of Conductor mm² 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 1 x 500 1 x 630 1 x 800 1 x 1000
 Insulation Thickness (Min) mm 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40
Outer Sheath Thickness mm 1.70 1.70 1.80 1.80 1.90 1.90 2.00 2.10 2.20 2.30 2.40 2.50 2.60
Overall Diameter (Nom) mm 23.00 25.00 27.00 29.00 30.00 32.00 34.00 36.00 40.00 43.00 47.00 51.00 56.00
Cable Weight (Nom) Kg/Km 860 1100 1390 1650 1940 2310 2900 3520 4370 5450 6850 8950 10590
 Internal Bending Radius (Min) mm 460 500 540 580 600 640 680 720 800 860 940 1020 1120
d.c. Conductor Resistance @ 20°C (Max) Ω/Km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047 0.0366 0.0283 0.0221 0.0176
a.c. Conductor Resistance @ 90°C (Max) Ω/Km 0.494 0.342 0.247 0.196 0.159 0.128 0.0981 0.0792 0.0634 0.0511 0.0418 0.0351 0.0304
 Inductance mH/Km 0.405 0.379 0.360 0.345 0.337 0.328 0.312 0.301 0.292 0.282 0.275 0.269 0.265
Reactance @ 50Hz* Ω/Km 0.127 0.119 0.113 0.108 0.106 0.103 0.098 0.0946 0.0917 0.0886 0.0864 0.0845 0.0833
 Impedance @ 90°C & 50Hz Ω/Km 0.51 0.36 0.27 0.22 0.19 0.16 0.14 0.12 0.11 0.10 0.10 0.09 0.09
Capacitance (Max) μ/Km 0.26 0.29 0.33 0.37 0.39 0.42 0.47 0.52 0.59 0.65 0.72 0.8 0.89
Charging Current A/Km 0.52 0.58 0.66 0.74 0.78 0.84 0.94 1.04 1.18 1.30 1.44 1.60 1.78
Continuous Current Carrying Capacity (Laid Direct)* A 220 270 321 364 410 460 530 600 680 750 838 928 1003
Continuous Current Carrying Capacity (Ducts)* A 225 270 320 360 400 440 505 560 610 680 753 840 913
Continuous Current Carrying Capacity (Air)* A 250 310 375 430 490 565 660 760 880 1000 1140 1313 1423
Symmetrical Short Circuit Rating (Max)
90°C – 250°C for 1.0 sec kA 7.2 10.0 13.6 17.2 21.5 26.5 34.3 42.9 57.2 71.5 90.1 >100 >100
Earth Fault Short Circuit Rating (Max)
80°C – 200°C for 1.0 sec kA 1.3 1.5 1.6 1.7 1.8 1.9 2.1 2.3 2.5 2.8 3.0 3.3 3.6

Single Core – Class 2 Copper Conductor, XLPE Insulated, Copper Wire Screen, PVC (PE) Sheathed

Nominal Area of Conductor mm² 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 1 x 500 1 x 630 1 x 800 1 x 1000
 Insulation Thickness (Min) mm 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40
Outer Sheath Thickness mm 1.70 1.70 1.80 1.80 1.90 1.90 2.00 2.10 2.20 2.30 2.40 2.50 2.60
Overall Diameter (Nom) mm 25.00 27.00 29.00 30.00 32.00 33.00 36.00 38.00 42.00 45.00 49.00 53.00 58.00
Cable Weight (Nom) Kg/Km 1160 1390 1680 1940 2220 2580 3170 3780 4620 5690 7080 8810 10800
 Internal Bending Radius (Min) mm 500 540 580 600 640 660 720 760 840 900 980 1060 1160
d.c. Conductor Resistance @ 20°C (Max) Ω/Km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047 0.0366 0.0283 0.0221 0.0176
a.c. Conductor Resistance @ 90°C (Max) Ω/Km 0.494 0.342 0.247 0.196 0.159 0.128 0.0981 0.0792 0.0634 0.0511 0.0415 0.0348 0.0301
 Inductance mH/Km 0.416 0.388 0.368 0.352 0.345 0.333 0.321 0.311 0.299 0.290 0.281 0.276 0.269
Reactance @ 50Hz* Ω/Km 0.131 0.122 0.116 0.111 0.108 0.105 0.101 0.0977 0.0939 0.0911 0.0883 0.0867 0.0845
 Impedance @ 90°C & 50Hz Ω/Km 0.51 0.36 0.27 0.23 0.19 0.17 0.14 0.13 0.11 0.10 0.10 0.09 0.09
Capacitance (Max) μ/Km 0.26 0.29 0.33 0.37 0.39 0.42 0.47 0.52 0.59 0.65 0.72 0.8 0.89
Charging Current A/Km 0.51 0.58 0.66 0.74 0.78 0.84 0.94 1.04 1.18 1.30 1.44 1.60 1.78
Continuous Current Carrying Capacity (Laid Direct)* A 220 270 321 364 410 460 530 600 680 750 838 928 1003
Continuous Current Carrying Capacity (Ducts)* A 225 270 320 360 400 440 505 560 610 680 753 840 913
Continuous Current Carrying Capacity (Air)* A 250 310 375 430 490 565 660 760 880 1000 1140 1313 1423
Symmetrical Short Circuit Rating (Max)
90°C – 250°C for 1.0 sec kA 7.2 10.0 13.6 17.2 21.5 26.5 34.3 42.9 57.2 71.5 90.1 >100 >100
Earth Fault Short Circuit Rating (Max)
80°C – 200°C for 1.0 sec kA 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

Single Core – Class 2 Copper Conductor, XLPE Insulated, Copper Taped Screen, PVC (PE) Bedding, Galvanised Steel Wire Armour, PVC (PE) Sheathed

Nominal Area of Conductor mm² 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 1 x 500 1 x 630 1 x 800 1 x 1000
 Insulation Thickness (Min) mm 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40
 Inner Sheath Thickness mm 1.20 1.20 1.20 1.20 1.20 1.20 1.20 1.20 1.20 1.30 1.40 1.40 1.50
Aluminium Wire Armour Diameter mm 1.60 1.60 1.60 1.60 2.00 2.00 2.00 2.00 2.00 2.50 2.50 2.50 2.50
Outer Sheath Thickness mm 1.80 1.90 1.90 2.00 2.10 2.10 2.20 2.20 2.40 2.50 2.60 2.70 2.90
Overall Diameter (Nom) mm 29.00 31.00 33.00 35.00 37.00 38.00 41.00 43.00 47.00 51.00 55.00 60.00 64.00
Cable Weight (Nom) Kg/Km 1220 1500 1800 2110 2490 2900 3530 4160 5090 6400 7900 9720 11870
 Internal Bending Radius (Min) mm 435 465 495 525 555 570 615 645 705 765 825 900 960
d.c. Conductor Resistance @ 20°C (Max) Ω/Km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047 0.0366 0.0283 0.0221 0.0176
a.c. Conductor Resistance @ 90°C (Max) Ω/Km 0.494 0.342 0.247 0.196 0.159 0.128 0.0978 0.0788 0.0628 0.0503 0.0408 0.034 0.0292
 Inductance mH/Km 0.452 0.422 0.403 0.386 0.381 0.365 0.352 0.340 0.328 0.320 0.310 0.305 0.296
Reactance @ 50Hz* Ω/Km 0.142 0.133 0.127 0.121 0.12 0.115 0.111 0.107 0.103 0.101 0.0974 0.0958 0.093
 Impedance @ 90°C & 50Hz Ω/Km 0.51 0.37 0.28 0.23 0.20 0.17 0.15 0.13 0.12 0.11 0.11 0.10 0.10
Capacitance (Max) μ/Km 0.26 0.29 0.33 0.37 0.39 0.42 0.47 0.52 0.59 0.65 0.72 0.8 0.89
Charging Current A/Km 0.51 0.58 0.66 0.74 0.78 0.84 0.94 1.04 1.18 1.30 1.44 1.60 1.78
Continuous Current Carrying Capacity (Laid Direct)* A 221 270 321 363 410 455 520 580 650 710 761 812 868
Continuous Current Carrying Capacity (Ducts)* A 220 261 306 341 375 410 460 500 531 570 620 670 700
Continuous Current Carrying Capacity (Air)* A 251 310 376 431 490 562 650 740 840 931 1040 1163 1251
Symmetrical Short Circuit Rating (Max)
90°C – 250°C for 1.0 sec kA 7.2 10.0 13.6 17.2 21.5 26.5 34.3 42.9 57.2 71.5 90.1 >100 >100
Earth Fault Short Circuit Rating of Copper Tape (Max)
80°C – 200°C for 1.0 sec kA 0.7 0.7 0.8 0.9 0.9 1.0 1.1 1.1 1.3 1.4 1.5 1.7 1.8
Earth Fault Short Circuit Rating of Armour (Max)
80°C – 200°C for 1.0 sec kA 6.5 7.0 7.5 8.0 10.4 11.2 12.0 12.8 13.9 19.2 20.9 22.5 24.6

Three Core – Class 2 Copper Conductor, XLPE Insulated, Copper Taped Screen, PVC (PE) Bedding, Galvanised Steel Wire Armour, PVC (PE) Sheathed

Nominal Area of Conductor mm² 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 3 x 240   3 x 300 3 x 400
 Insulation Thickness (Min) mm 3.4 3.4 3.4 3.4 3.40 3.4 3.4 3.4 3.4 3.40 3.40 3.40
 Inner Sheath Thickness mm 1.2 1.3 1.3 1.4 1.40 1.5 1.6 1.6 1.7 1.80 1.90 2.00
Galvanised Steel Wire Armour Diameter mm 2 2.5 2.5 2.5 2.50 2.5 2.5 2.5 2.5 3.15 3.15 3.15
Outer Sheath Thickness mm 2.3 2.4 2.5 2.6 2.70 2.8 3 3.1 3.2 3.40 3.60 3.80
Overall Diameter (Nom) mm 44 49 52 54 58.00 63 67 70 74 81.00    86.00 94.00
Cable Weight (Nom) Kg/Km 3130 4070 4590 5180 6120 7310 8410 9420 10860 13990    16290 19500
 Internal Bending Radius (Min) mm 528 588 624 648 696 756 804 840 888 972 1032 1128
d.c. Conductor Resistance @ 20°C (Max) Ω/Km 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754   0.0601 0.047
a.c. Conductor Resistance @ 90°C (Max) Ω/Km 1.47 0.927 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.1   0.0819 0.0667
 Inductance mH/Km 0.443 0.41 0.376 0.364 0.341 0.323 0.309 0.303 0.294 0.283    0.275 0.265
Reactance @ 50Hz* Ω/Km 0.139 0.129 0.118 0.114 0.107 0.101 0.0971 0.0952 0.0924 0.0889   0.0864 0.0833
 Impedance @ 90°C & 50Hz Ω/Km 1.48 0.94 0.68 0.51 0.36 0.27 0.22 0.19 0.16 0.13 0.12 0.11
Capacitance (Max) μ/Km 0.18 0.21 0.24 0.26 0.29 0.33 0.37 0.39 0.42 0.47 0.52 0.59
Charging Current A/Km 0.36 0.41 0.48 0.52 0.58 0.66 0.74 0.78 0.84 0.94 1.04 1.18
Continuous Current Carrying Capacity (Laid Direct) A 119 152 181 213 260 309 349 390 436 499 553 619
Continuous Current Carrying Capacity (Ducts) A 102 131 156 182 224 263 306 342 379 438 481 552
Continuous Current Carrying Capacity (Air) A 126 163 197 236 291 353 402 454 515 600 676 768
Symmetrical Short Circuit Rating (Max)
90°C – 250°C for 1.0 sec kA 2.3 3.6 5 7.2 10.0 13.6 17.2 21.5 26.5 34.3 42.9 57.2
Earth Fault Short Circuit Rating of Copper Tape (Max)
80°C – 200°C for 1.0 sec kA 1.1 1.2 1.3 1.3 1.5 1.6 1.7 1.8 1.9 2.1 2.3 2.5
Earth Fault Short Circuit Rating of Armour (Max)
80°C – 200°C for 1.0 sec kA 2.3 3.6 5 7.2 10.0 12.9 13.8 14.5 15.4 21.2 22.6 24.7

Single Core – Class 2 Aluminium Conductor, XLPE Insulated, Copper Taped Screen, PVC (PE) Sheathed

Nominal Area of Conductor mm² 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 1 x 500 1 x 630 1 x 800 1 x 1000
 Insulation Thickness (Min) mm 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40
Outer Sheath Thickness mm 1.70 1.70 1.80 1.80 1.90 1.90 2.00 2.10 2.20 2.30 2.40 2.50 2.60
Overall Diameter (Nom) mm 23.00 25.00 27.00 29.00 30.00 32.00 34.00 36.00 40.00 43.00 47.00 54.00 59.00
Cable Weight (Nom) Kg/Km 590 690 820 930 1050 1210 1440 1690 2020 2420 2940 3670 4410
 Internal Bending Radius (Min) mm 460 500 540 580 600 640 680 720 800 860 940 1080 1180
d.c. Conductor Resistance @ 20°C (Max) Ω/Km 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469 0.0367 0.0291
a.c. Conductor Resistance @ 90°C (Max) Ω/Km 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.13 0.102 0.0804 0.0639 0.052 0.0435
 Inductance mH/Km 0.395 0.374 0.355 0.345 0.337 0.322 0.309 0.300 0.291 0.282 0.275 0.265 0.260
Reactance @ 50Hz* Ω/Km 0.1241 0.1175 0.1115 0.1084 0.1059 0.1012 0.0971 0.0943 0.0914 0.0886 0.0864 0.0833 0.0817
 Impedance @ 90°C & 50Hz Ω/Km 0.83 0.58 0.43 0.34 0.29 0.23 0.19 0.16 0.14 0.12 0.11 0.10 0.09
Capacitance (Max) μ/Km 0.26 0.3 0.34 0.37 0.39 0.43 0.48 0.53 0.59 0.65 0.72 0.86 0.95
Charging Current A/Km 0.52 0.60 0.68 0.74 0.78 0.86 0.96 1.06 1.18 1.30 1.44 1.72 1.90
Continuous Current Carrying Capacity (Laid Direct)* A 172 210 250 284 320 360 415 475 540 610 686 776 855
Continuous Current Carrying Capacity (Ducts)* A 175 215 255 285 315 350 405 455 510 570 640 713 792
Continuous Current Carrying Capacity (Air)* A 195 240 300 335 380 443 512 600 700 810 930 1096 1211
Symmetrical Short Circuit Rating (Max)
90°C – 250°C for 1.0 sec kA 4.7 6.6 8.9 11.3 14.1 17.4 22.6 28.2 37.6 47.0 59.2 75.2 94
Earth Fault Short Circuit Rating (Max)
80°C – 200°C for 1.0 sec kA 1.4 1.5 1.6 1.7 1.8 2.0 2.1 2.3 2.5 2.8 3.0 3.5 3.8

Single Core – Class 2 Aluminium Conductor, XLPE Insulated, Copper Wire Screen, PVC (PE) Sheathed

Nominal Area of Conductor mm² 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 1 x 500 1 x 630 1 x 800 1 x 1000
 Insulation Thickness (Min) mm 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40
Outer Sheath Thickness mm 1.70 1.70 1.80 1.80 1.90 1.90 2.00 2.10 2.20 2.30 2.40 2.50 2.60
Overall Diameter (Nom) mm 25.00 27.00 29.00 30.00 32.00 33.00 36.00 38.00 42.00 45.00 49.00 56.00 61.00
Cable Weight (Nom) Kg/Km 890 980 1110 1210 1330 1480 1700 1950 2270 2660 3170 3880 4600
 Internal Bending Radius (Min) mm 500 540 580 600 640 680 720 780 840 900 980 1120 1220
d.c. Conductor Resistance @ 20°C (Max) Ω/Km 0.641 0.443 0.32 0.253 0.206 0.164 0.125 0.1 0.0778 0.0605 0.0469 0.0367 0.0291
a.c. Conductor Resistance @ 90°C (Max) Ω/Km 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.13 0.102 0.0803 0.0637 0.0518 0.0432
 Inductance mH/Km 0.409 0.385 0.365 0.352 0.345 0.330 0.320 0.308 0.298 0.290 0.281 0.271 0.264
Reactance @ 50Hz* Ω/Km 0.1285 0.121 0.1147 0.1106 0.1084 0.1037 0.1005 0.0968 0.0936 0.0911 0.0883 0.0851 0.0829
 Impedance @ 90°C & 50Hz Ω/Km 0.83 0.58 0.43 0.34 0.29 0.24 0.19 0.16 0.14 0.12 0.11 0.10 0.09
Capacitance (Max) μ/Km 0.26 0.3 0.34 0.37 0.39 0.43 0.48 0.53 0.59 0.65 0.72 0.86 0.95
Charging Current A/Km 0.51 0.60 0.68 0.74 0.78 0.86 0.96 1.06 1.18 1.30 1.44 1.72 1.90
Continuous Current Carrying Capacity (Laid Direct)* A 172 210 250 284 320 360 415 475 540 610 686 776 855
Continuous Current Carrying Capacity (Ducts)* A 175 215 255 285 315 350 405 455 510 570 640 713 792
Continuous Current Carrying Capacity (Air)* A 195 240 300 335 380 443 512 600 700 810 930 1096 1211
Symmetrical Short Circuit Rating (Max)
90°C – 250°C for 1.0 sec kA 4.7 6.6 8.9 11.3 14.1 17.4 22.6 28.2 37.6 47.0 59.2 75.2 94
Earth Fault Short Circuit Rating (Max)
80°C – 200°C for 1.0 sec kA 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

Single Core – Class 2 Aluminium Conductor, XLPE Insulated, Copper Taped Screen, PVC (PE) Bedding, Galvanised Steel Wire Armour, PVC (PE) Sheathed

Nominal Area of Conductor mm² 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 1 x 500 1 x 630 1 x 800 1 x 1000
 Insulation Thickness (Min) mm 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40
 Inner Sheath Thickness mm 1.20 1.20 1.20 1.20 1.20 1.20 1.20 1.20 1.20 1.30 1.40 1.40 1.50
Aluminium Wire Armour Diameter mm 1.60 1.60 1.60 1.60 2.00 2.00 2.00 2.00 2.00 2.50 2.50 2.50 2.50
Outer Sheath Thickness mm 1.80 1.90 1.90 2.00 2.10 2.10 2.20 2.20 2.40 2.50 2.60 2.70 2.90
Overall Diameter (Nom) mm 29.00 31.00 33.00 35.00 37.00 38.00 41.00 43.00 47.00 51.00 55.00 62.00 67.00
Cable Weight (Nom) Kg/Km 950 1090 1230 1380 1600 1790 2060 2350 2740 3370 3990 4850 5750
 Internal Bending Radius (Min) mm 435 465 495 525 555 585 615 660 705 765 825 930 1005
d.c. Conductor Resistance @ 20°C (Max) Ω/Km 0.641 0.443 0.32 0.253 0.206 0.164 0.125 0.1 0.0778 0.0605 0.0469 0.0367 0.0291
a.c. Conductor Resistance @ 90°C (Max) Ω/Km 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.13 0.102 0.0799 0.0632 0.0512 0.0425
 Inductance mH/Km 0.441 0.417 0.397 0.386 0.381 0.364 0.349 0.338 0.327 0.320 0.310 0.297 0.289
Reactance @ 50Hz* Ω/Km 0.1385 0.131 0.1247 0.1213 0.1197 0.1144 0.1096 0.1062 0.1027 0.1005 0.0974 0.0933 0.0908
 Impedance @ 90°C & 50Hz Ω/Km 0.83 0.58 0.43 0.35 0.29 0.24 0.19 0.17 0.14 0.13 0.12 0.11 0.10
Capacitance (Max) μ/Km 0.26 0.3 0.34 0.37 0.39 0.43 0.48 0.53 0.59 0.65 0.72 0.86 0.95
Charging Current A/Km 0.52 0.60 0.68 0.74 0.78 0.86 0.96 1.06 1.18 1.30 1.44 1.72 1.90
Continuous Current Carrying Capacity (Laid Direct)* A 172 210 250 284 316 358 412 461 519 577 642 704 767
Continuous Current Carrying Capacity (Ducts)* A 170 210 245 275 300 335 380 420 455 500 550 600 640
Continuous Current Carrying Capacity (Air)* A 196 240 295 337 380 442 514 586 679 770 880 1002 1100
Symmetrical Short Circuit Rating (Max)
90°C – 250°C for 1.0 sec kA 4.7 6.6 8.9 11.3 14.1 17.4 22.6 28.2 37.6 47.0 59.2 75.2 94
Earth Fault Short Circuit Rating of Copper Tape (Max)
80°C – 200°C for 1.0 sec kA 0.7 0.7 0.8 0.9 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.8 1.9
Earth Fault Short Circuit Rating of Armour (Max)
80°C – 200°C for 1.0 sec kA 4.7 6.6 7.5 8.0 10.4 11.2 12.0 13.1 13.9 19.2 20.9 23.8 25.9

Three Core – Class 2 Aluminium Conductor, XLPE Insulated, Copper Taped Screen, PVC (PE) Bedding, Galvanised Steel Wire Armour, PVC (PE) Sheathed

Nominal Area of Conductor mm² 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185     3 x 240   3 x 300    3 x 400
 Insulation Thickness (Min) mm 3.4 3.4 3.4 3.4 3.40 3.4 3.4 3.4 3.4       3.40     3.40 3.40
 Inner Sheath Thickness mm 1.2 1.3 1.3 1.4 1.40 1.5 1.6 1.6 1.7       1.80     1.90 2.00
Galvanised Steel Wire Armour Diameter mm 2 2.5 2.5 2.5 2.50 2.5 2.5 2.5 2.5       3.15     3.15 3.15
Outer Sheath Thickness mm 2.3 2.4 2.5 2.6 2.70 2.8 3 3.1 3.2       3.40     3.60 3.80
Overall Diameter (Nom) mm 44 50 52 55 59.00 63 67 70 75      81.00    87.00 94.00
Cable Weight (Nom) Kg/Km 2890 3620 3950 4400 4930 5600 6220 6710 7570      9560    10850 12450
 Internal Bending Radius (Min) mm 528 600 624 660 708 756 804 840 900 972     1044 1128
d.c. Conductor Resistance @ 20°C (Max) Ω/Km 1.91 1.2 0.868 0.641 0.443 0.32 0.253 0.206 0.164      0.125     0.10    0.0778
a.c. Conductor Resistance @ 90°C (Max) Ω/Km 2.45 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211      0.163    0.131 0.104
 Inductance mH/Km 0.435 0.404 0.376 0.358 0.338 0.32 0.309 0.303 0.292      0.283    0.272 0.265
Reactance @ 50Hz* Ω/Km 0.1367 0.1269 0.1181 0.1125 0.1062 0.1005 0.0971 0.0952 0.0917     0.0889   0.0855    0.0833
 Impedance @ 90°C & 50Hz Ω/Km 2.45 1.55 1.12 0.83 0.58 0.42 0.34 0.28 0.23       0.19     0.16 0.13
Capacitance (Max) μ/Km 0.19 0.22 0.24 0.26 0.30 0.34 0.37 0.39 0.43       0.48     0.53 0.59
Charging Current A/Km 0.38 0.44 0.48 0.52 0.60 0.68 0.74 0.78 0.86       0.96     1.06 1.18
Continuous Current Carrying Capacity (Laid Direct) A 92 118 141 166 202 241 272 304 343 395     440 500
Continuous Current Carrying Capacity (Ducts) A 79 101 121 141 174 205 239 267 297 347     383 446
Continuous Current Carrying Capacity (Air) A 97 127 153 183 226 274 314 354 404 473     536 618
Symmetrical Short Circuit Rating (Max)
90°C – 250°C for 1.0 sec kA 1.5 2.4 3.3 4.7 6.6 8.9 11.3 14.1 17.4       22.6     28.2 37.6
Earth Fault Short Circuit Rating of Copper Tape (Max)
80°C – 200°C for 1.0 sec kA 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 2 2.1      2.3 2.5
Earth Fault Short Circuit Rating of Armour (Max)
80°C – 200°C for 1.0 sec kA 1.5 2.4 3.3 4.7 6.6 8.9 11.3 14.1 15.6       21.2     22.9 25.1