For inquiries about our products or price list , please leave your email to us and we will be in touch within 24 hour
XLPE Control Cable for controlling electrical equipment and instrument meters, monitoring and controlling return circuit, protecting and measuring in power distribution with rated voltage up to 450/750V(0.6/1KV) A.C.
Electrical performance U0/U:
450/750V
Chemical performance:
chemical, UV&oil resistance
Mechanical performance:
Minimum bending radius:x10 cable diameter
Terminal performance :
Maximum service temperature:90℃
Maximum short-circuit temperature:250°C(max. 5s)Minimum service temperature:-40°℃
Fire performance:
Flame non-propagation base on lEC 60332-1Standard
XLPE insulated control cables |
||
model |
name |
application |
KYJV | XLPE insulated PVC sheathed control cable | For laying indoors, cable trench, pipeline and other fixed places |
KYJYP | XLPE insulated PVC sheathed control cable braided shield | For laying indoors, cable trench, pipeline and other requirements on shielding |
KYJVP2 | XLPE insulated PVC sheathed copper shielded control cable | For laying indoors, cable trench, pipeline and other requirements on shielding |
KYJVP3 | XLPE insulated PVC sheathed aluminum composite tape shield control cable | For laying indoors, cable trench, pipeline and other requirements on shielding |
KYJV22 | XLPE insulated PVC sheathed control cable | For laying indoors, cable trench, pipeline, direct burial withstand greater mechanical force fixed installation |
KYJVP2-22 | XLPE insulated PVC sheathed copper tape shield steel tape armored control cable | For laying indoors, cable trench, pipeline, direct burial withstand greater mechanical force fixed installation |
KYJV32 | XLPE insulated PVC sheathed steel wire armored control cable | Suitable for water or high drop area, can bear external mechanical forces and considerable tension |
KYJVR | XLPE insulated PVC sheathed control cable | For laying indoors, movable and flexible |
KYJVRP | XLPE insulated PVC sheathed control cable braided shield | For laying indoors, movable and flexible shield occasions |
NOTE: This series’ core of cable is recommended for: 2、3、4、5、7、8、10、12、14、16、19、24、27、30、37、44、48、52、61. |
1)Conductor
2)Insulation
3)Filler
4)Binder tape
5)Inner covering
6)Armour
7)Over Sheath
Cable Marking:
printing, embossing, engraving
Packing Materials:
wooden drum, steel drum, steel-wooden drum
IEC 60502-1 IEC60227 IEC 60228, etc.
Other standards are available
For inquiries about our products or price list , please leave your email to us and we will be in touch within 24 hour