AEIC CS8-07 35kV Type MV 105 Cable Three Core 100% / 133% EPR/PVC

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

Type MV 105 Cable is suitable for use in wet or dry locations at maximum operating temperature of 105°C for normal operation; 140°C for emergency overload conditions; and 250°C for short circuit conditions. Cables may be installed in conduit, duct or aerially when properly supported by a Messenger.

Construction

Conductor:
Class B Compressed concentric strand or soft drawn annealed copper per ASTM B3.
Class A or B Compressed concentric stranded aluminum alloy 1350 per ASTM B 231. Stranded conductors are water-blocked with conductor filling compound.

Conductor Shield:
Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation

Insulation:
Ethylene Propylene Rubber EPR

Insulation Shield:
Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.

Metallic Shield:
The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap. A Mylar ribbon is longitudinally applied under the copper tape shield for phase identification - 1C w/Red, 1C w/Blue, and 1C w/None.

Grounding Conductors:
Three bare stranded copper conductor, one in each interstice.

Fillers:
Non hygroscopic fillers, forming a firm and cylindrical cable core.

Binder Tape:
A binder tape is applied to maintain core symmetry and mechanical stability.

Jacket:
Black flame retardant Polyvinyl Chloride (PVC).

AEIC-CS8-07-35kV-MV-105-Cable-Copper-Aluminum-3-Conductor-(2)

Cable Marking and Packing Materials

Cable Marking:
printing, embossing ,engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Standards

- AEIC CS8, Specifications for Shielded Power Cable, 5-46kV
- ICEA S-93-639, 5-46 kV Shielded Power Cable
- ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
- UL 1072 MV-105
- IEEE- IEEE 383 Flame Test
- For 105°C continuous, 140°C emergency, 250°C short-circuit operation.
- CSA Standard C68.5-07 File # 257759 Primary Shielded and Concentric Neutral Cable for Distribution

35kV CU 100% MV-105 Cable Specification

Size Insulation
Thickness
No. of
Ground
Wires
Size
of
Ground
Wires
Conductor
Diameter
Insulation
Diameter
Insulation
Shield
Diameter
Overall
Jacket
Diameter
Approximate
Weight
Minimum
Bending
Radius
Ampacity
90ºC
in Duct
Ampacity
90ºC
in Air
AWG
or
KCMIL
mils No. mils in in in in lb/MFT in Amps Amps
1/0 345 3 8 0.364 1.11 1.18 2.88 3761 21 195 215
2/0 345 3 8 0.408 1.15 1.22 2.97 4151 21 220 245
3/0 345 3 7 0.458 1.2 1.27 3.08 4662 22 250 285
4/0 345 3 7 0.515 1.26 1.33 3.21 5245 23 285 325
250 345 3 7 0.561 1.31 1.38 3.32 5762 24 310 360
350 345 3 6 0.664 1.41 1.48 3.54 7060 25 375 435
500 345 3 5 0.794 1.54 1.63 3.86 9015 27 450 535

35kV CU 133% MV-105 Cable Specification

Size Insulation
Thickness
No. of
Ground
Wires
Size
of
Ground
Wires
Conductor
Diameter
Insulation
Diameter
Insulation
Shield
Diameter
Overall
Jacket
Diameter
Approximate
Weight
Minimum
Bending
Radius
Ampacity
90ºC
in Duct
Ampacity
90ºC
in Air
AWG
or
KCMIL
mils No. mils in in in in lb/MFT in Amps Amps
1/0 420 3 8 0.364 1.26 1.33 3.21 4356 23 195 215
2/0 420 3 8 0.408 1.3 1.38 3.31 4761 24 220 245
3/0 420 3 7 0.458 1.35 1.43 3.41 5291 24 250 285
4/0 420 3 7 0.515 1.41 1.48 3.54 5895 25 285 325
250 420 3 7 0.561 1.46 1.54 3.65 6430 26 310 360
350 420 3 6 0.664 1.57 1.65 3.91 7854 28 375 435
500 420 3 5 0.794 1.7 1.78 4.19 9775 30 450 535

35kV AL 100% MV-105 Cable Specification

Size Insulation
Thickness
No. of
Ground
Wires
Size
of
Ground
Wires
Conductor
Diameter
Insulation
Diameter
Insulation
Shield
Diameter
Overall
Jacket
Diameter
Approximate
Weight
Minimum
Bending
Radius
Ampacity
90ºC
in Duct
Ampacity
90ºC
in Air
AWG
or
KCMIL
mils No. mils in in in in lb/MFT in Amps Amps
1/0 345 3 10 0.364 1.11 1.18 2.88 3031 21 150 170
2/0 345 3 8 0.408 1.15 1.22 2.97 3303 21 170 190
3/0 345 3 8 0.458 1.2 1.27 3.08 3555 22 195 220
4/0 345 3 8 0.515 1.26 1.33 3.21 3859 23 220 255
250 345 3 8 0.561 1.31 1.38 3.32 4132 24 245 280
350 345 3 7 0.664 1.41 1.48 3.54 4785 25 295 345
500 345 3 6 0.794 1.54 1.63 3.86 5771 27 355 425

35kV AL 133% MV-105 Cable Specification

Size Insulation
Thickness
No. of
Ground
Wires
Size
of
Ground
Wires
Conductor
Diameter
Insulation
Diameter
Insulation
Shield
Diameter
Overall
Jacket
Diameter
Approximate
Weight
Minimum
Bending
Radius
Ampacity
90ºC
in Duct
Ampacity
90ºC
in Air
AWG
or
KCMIL
mils No. mils in in in in lb/MFT in Amps Amps
1/0 420 3 10 0.364 1.26 1.33 3.21 3626 23 150 170
2/0 420 3 8 0.408 1.3 1.38 3.31 3914 24 170 190
3/0 420 3 8 0.458 1.35 1.43 3.41 4184 24 195 220
4/0 420 3 8 0.515 1.41 1.48 3.54 4509 25 220 255
250 420 3 8 0.561 1.46 1.54 3.65 4800 26 245 280
350 420 3 7 0.664 1.57 1.65 3.91 5580 28 295 345
500 420 3 6 0.794 1.7 1.78 4.19 6531 30 355 425