AEIC CS8-07 MV 105 15kV Cable 3 Core Copper / Aluminum Conductor

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

MV 105 15kV Cable is For use in overhead, direct burial, cable tray, conduit, and underground duct installations as permitted by the National Electric Code.
The 3 Core MV 105 cable is capable of operating continuously with a conductor temperature not to exceed 1050 degree for normal operation, 1400 degree for emergency overload conditions, and 2500 degree for short circuit conditions.

Construction

Conductor:
Annealed bare copper Compact, Class B stranding. ***Also available in Class B compressed copper..

Conductor Shield:
Extruded thermoset semi-conducting stress control layer over conductor

Insulation:
EPR-based insulation.

Insulation Shield:
Thermoset semi-conducting polymeric layer free stripping from insulation.

Metallic Shield:
5 mils annealed copper tape with an overlap of 25%

Grounding Conductors:
1 Class B copper conductor per ASTM B3 and ASTM B8.

Fillers:
Non hygroscopic fillers, forming a firm and cylindrical cable core.

Binder Tape:
Poly glass tape

Jacket:
Black flame retardant PVC jacket .

AEIC-CS8-07-15kV-MV-105-Cable-Copper-Aluminum-3-Conductor-(2)

Cable Marking and Packing Materials

Cable Marking:
printing, embossing ,engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Standards

AEIC CS8 Standard for Shielded Power Cable, 5-46kV
ICEA S-93-639, 5-46 kV Shielded Power Cable
ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
UL 1072 MV-105 Standard

CU 100% MV 105 15kV Cable Specification

Size Insulation
Thickness
No. of
Ground
Wires
Size
of
Ground
Wires
Conductor
Diameter
Insulation
Diameter
Insulation
Shield
Diameter
Overall
Jacket
Diameter
Approximate
Weight
Minimum
Bending
Radius
Ampacity
90ºC
in Duct
Ampacity
90ºC
in Air
AWG
or
KCMIL
mils No. mils in in in in lb/MFT in Amps Amps
2 175 3 10 0.284 0.68 0.74 1.87 1888 14 150 165
1 175 3 8 0.324 0.72 0.78 1.96 2179 14 170 185
1/0 175 3 8 0.364 0.76 0.82 2.04 2466 15 195 215
2/0 175 3 8 0.408 0.81 0.86 2.14 2813 15 220 245
3/0 175 3 7 0.458 0.86 0.91 2.24 3275 16 250 285
4/0 175 3 7 0.515 0.91 0.97 2.37 3803 17 285 325
250 175 3 7 0.561 0.97 1.02 2.48 4268 18 310 360
350 175 3 6 0.664 1.07 1.14 2.74 5529 20 375 435
500 175 3 5 0.794 1.2 1.27 3.08 7447 22 450 535
750 175 3 4 0.974 1.39 1.46 3.48 10333 25 545 670
1000 175 3 4 1.124 1.54 1.62 3.84 13138 27 615 770

CU 133% MV 105 15kV Cable Specification

Size Insulation
Thickness
No. of
Ground
Wires
Size
of
Ground
Wires
Conductor
Diameter
Insulation
Diameter
Insulation
Shield
Diameter
Overall
Jacket
Diameter
Approximate
Weight
Minimum
Bending
Radius
Ampacity
90ºC
in Duct
Ampacity
90ºC
in Air
AWG
or
KCMIL
mils No. mils in in in in lb/MFT in Amps Amps
2 220 3 10 0.284 0.77 0.83 2.06 2124 15 150 165
1 220 3 8 0.324 0.81 0.87 2.15 2424 16 170 185
1/0 220 3 8 0.364 0.85 0.91 2.24 2719 16 195 215
2/0 220 3 8 0.408 0.9 0.95 2.33 3075 17 220 245
3/0 220 3 7 0.458 0.95 1 2.44 3548 18 250 285
4/0 220 3 7 0.515 1 1.06 2.56 4088 18 285 325
250 220 3 7 0.561 1.06 1.13 2.71 4627 19 310 360
350 220 3 6 0.664 1.16 1.23 2.99 6018 21 375 435
500 220 3 5 0.794 1.29 1.36 3.27 7808 23 450 535
750 220 3 4 0.974 1.48 1.55 3.68 10733 26 545 670
1000 220 3 4 1.124 1.63 1.71 4.04 13574 29 615 770

AL 100% MV 105 15kV Cable Specification

Size Insulation
Thickness
No. of
Ground
Wires
Size
of
Ground
Wires
Conductor
Diameter
Insulation
Diameter
Insulation
Shield
Diameter
Overall
Jacket
Diameter
Approximate
Weight
Minimum
Bending
Radius
Ampacity
90ºC
in Duct
Ampacity
90ºC
in Air
AWG
or
KCMIL
mils No. mils in in in in lb/MFT in Amps Amps
2 175 3 10 0.284 0.68 0.74 1.87 1469 14 115 125
1 175 3 10 0.324 0.72 0.78 1.96 1590 14 135 145
1/0 175 3 10 0.364 0.76 0.82 2.04 1736 15 150 170
2/0 175 3 8 0.408 0.81 0.86 2.14 1965 15 170 190
3/0 175 3 8 0.458 0.86 0.91 2.24 2168 16 195 220
4/0 175 3 8 0.515 0.91 0.97 2.37 2416 17 220 255
250 175 3 8 0.561 0.97 1.02 2.48 2638 18 245 280
350 175 3 7 0.664 1.07 1.14 2.74 3254 20 295 345
500 175 3 6 0.794 1.2 1.27 3.08 4203 22 355 425
750 175 3 5 0.974 1.39 1.46 3.48 5459 25 440 540
1000 175 3 4 1.124 1.54 1.62 3.84 6737 27 510 635

AL 133% MV 105 15kV Cable Specification

Size Insulation
Thickness
No. of
Ground
Wires
Size
of
Ground
Wires
Conductor
Diameter
Insulation
Diameter
Insulation
Shield
Diameter
Overall
Jacket
Diameter
Approximate
Weight
Minimum
Bending
Radius
Ampacity
90ºC
in Duct
Ampacity
90ºC
in Air
AWG
or
KCMIL
mils No. mils in in in in lb/MFT in Amps Amps
2 220 3 10 0.284 0.77 0.83 2.06 1705 15 115 125
1 220 3 10 0.324 0.81 0.87 2.15 1834 16 135 145
1/0 220 3 10 0.364 0.85 0.91 2.24 1989 16 150 170
2/0 220 3 8 0.408 0.9 0.95 2.33 2227 17 170 190
3/0 220 3 8 0.458 0.95 1 2.44 2441 18 195 220
4/0 220 3 8 0.515 1 1.06 2.56 2701 18 220 255
250 220 3 8 0.561 1.06 1.13 2.71 2997 19 245 280
350 220 3 7 0.664 1.16 1.23 2.99 3743 21 295 345
500 220 3 6 0.794 1.29 1.36 3.27 4564 23 355 425
750 220 3 5 0.974 1.48 1.55 3.68 5859 26 440 540
1000 220 3 4 1.124 1.63 1.71 4.04 7173 29 510 635