AEIC CS8-07 MV 105 5kV Cable Copper / Aluminum 3 Conductor

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

MV 105 5kV Cable offers an economical, rugged and reliable alternative to labor-intensive cable in conduit wiring methods.
Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced not more than six feet apart.
MV 105 5kV Cable Installed in both exposed and concealed work, wet or dry locations, directly buried.

Construction

Conductor:
Class B copper conductor as per ASTM B3.
Or Class A or B aluminum alloy 1350 conductor as per ASTM B231. Stranded conductors are water-blocked with conductor filling compound.

Conductor Shield:
Extruded thermosetting semiconducting shield

Insulation:
Extruded TRXLPE as defined in ANSI/ICEA S-94-649

Insulation Shield:
Extruded thermosetting semiconducting shield

Metallic Shield:
The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap. A Mylar ribbon is longitudinally applied under the copper tape shield for phase identification - 1C w/Red, 1C w/Blue, and 1C w/None.

Grounding Conductors:
Three bare stranded copper conductor.

Fillers:
Non hygroscopic fillers.

Binder Tape:
Poly glass tape.

Jacket:
Black, sunlight resistant, flame retardant PVC jacket tightly applied over the binder tape.

AEIC-CS8-07-5kV-MV-105-Cable-Copper-Aluminum-3-Conductor-(2)

1.Conductor(CU)
2.Conductor Shield
3.Insulation
4.Insulation Shield
5.Metallic Shield

6.Grounding Conductors
7.Fillers
8.Binder Tape
9.Jacket

AEIC-CS8-07-5kV-MV-105-Cable-Copper-Aluminum-3-Conductor-(3)

1.Conductor(AL)
2.Conductor Shield
3.Insulation
4.Insulation Shield
5.Metallic Shield

6.Grounding Conductors
7.Fillers
8.Binder Tape
9.Jacket

Cable Marking and Packing Materials

Cable Marking:
printing, embossing ,engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Standards

- AEIC CS8, Specifications for Shielded Power Cable, 5-46kV
- ICEA S-93-639, 5-46 kV Shielded Power Cable
- ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
- UL 1072 MV-105
- IEEE- IEEE 383 Flame Test
- For 105°C continuous, 140°C emergency, 250°C short-circuit operation.
- CSA Standard C68.5-07 File # 257759 Primary Shielded and Concentric Neutral Cable for Distribution

CU 100% MV 105 5kV Cable Specification

Size Insulation
Thickness
No. of
Ground
Wires
Size
of
Ground
Wires
Conductor
Diameter
Insulation
Diameter
Insulation
Shield
Diameter
Overall
Jacket
Diameter
Approximate
Weight
Minimum
Bending
Radius
Ampacity
90ºC
in Duct
Ampacity
90ºC
in Air
AWG
or
KCMIL
mils No. mils in in in in lb/MFT in Amps Amps
4 90 3 10 0.226 0.45 0.51 1.32 1097 10 100 105
2 90 3 10 0.284 0.51 0.57 1.44 1412 11 135 140
1 90 3 8 0.324 0.55 0.61 1.53 1682 11 155 160
1/0 90 3 8 0.364 0.59 0.65 1.61 1948 12 175 185
2/0 90 3 8 0.408 0.64 0.69 1.71 2271 12 200 215
3/0 90 3 7 0.458 0.69 0.74 1.88 2812 14 230 250
4/0 90 3 7 0.515 0.74 0.8 2 3317 15 265 285
250 90 3 7 0.561 0.8 0.85 2.11 3761 15 290 320
350 90 3 6 0.664 0.9 0.95 2.34 4918 17 355 395
500 90 3 5 0.794 1.03 1.1 2.65 6668 19 430 485
750 90 3 4 0.974 1.22 1.29 3.12 9629 22 530 615
1000 90 3 4 1.124 1.37 1.44 3.44 12287 25 600 705

CU 133% MV 105 5kV Cable Specification

Size Insulation
Thickness
No. of
Ground
Wires
Size
of
Ground
Wires
Conductor
Diameter
Insulation
Diameter
Insulation
Shield
Diameter
Overall
Jacket
Diameter
Approximate
Weight
Minimum
Bending
Radius
Ampacity
90ºC
in Duct
Ampacity
90ºC
in Air
AWG
or
KCMIL
mils No. mils in in in in lb/MFT in Amps Amps
4 115 3 10 0.226 0.5 0.56 1.42 1193 10 100 105
2 115 3 10 0.284 0.56 0.62 1.55 1515 11 135 140
1 115 3 8 0.324 0.6 0.66 1.64 1789 12 155 160
1/0 115 3 8 0.364 0.64 0.7 1.78 2158 13 175 185
2/0 115 3 8 0.408 0.69 0.74 1.88 2493 14 200 215
3/0 115 3 7 0.458 0.74 0.79 1.99 2941 14 230 250
4/0 115 3 7 0.515 0.79 0.85 2.11 3453 15 265 285
250 115 3 7 0.561 0.85 0.9 2.22 3903 16 290 320
350 115 3 6 0.664 0.95 1 2.44 5072 18 355 395
500 115 3 5 0.794 1.08 1.15 2.76 6839 20 430 485
750 115 3 4 0.974 1.27 1.34 3.22 9829 23 530 615
1000 115 3 4 1.124 1.42 1.49 3.55 12504 25 600 705

AL 100% MV 105 5kV Cable Specification

Size Insulation
Thickness
No. of
Ground
Wires
Size
of
Ground
Wires
Conductor
Diameter
Insulation
Diameter
Insulation
Shield
Diameter
Overall
Jacket
Diameter
Approximate
Weight
Minimum
Bending
Radius
Ampacity
90ºC
in Duct
Ampacity
90ºC
in Air
AWG
or
KCMIL
mils No. mils in in in in lb/MFT in Amps Amps
4 90 3 10 0.226 0.45 0.51 1.32 833 10 80 81
2 90 3 10 0.284 0.51 0.57 1.44 993 11 105 110
1 90 3 10 0.324 0.55 0.61 1.53 1093 11 120 125
1/0 90 3 10 0.364 0.59 0.65 1.61 1218 12 140 145
2/0 90 3 8 0.408 0.64 0.69 1.77 1522 13 160 170
3/0 90 3 8 0.458 0.69 0.74 1.88 1705 14 180 195
4/0 90 3 8 0.515 0.74 0.8 2 1930 15 205 225
250 90 3 8 0.561 0.8 0.85 2.11 2131 15 230 250
350 90 3 7 0.664 0.9 0.95 2.34 2643 17 280 310
500 90 3 6 0.794 1.03 1.1 2.65 3424 19 340 385
750 90 3 5 0.974 1.22 1.29 3.12 4755 22 425 495
1000 90 3 4 1.124 1.37 1.44 3.44 5886 25 495 585

AL 133% MV 105 5kV Cable Specification

Size Insulation
Thickness
No. of
Ground
Wires
Size
of
Ground
Wires
Conductor
Diameter
Insulation
Diameter
Insulation
Shield
Diameter
Overall
Jacket
Diameter
Approximate
Weight
Minimum
Bending
Radius
Ampacity
90ºC
in Duct
Ampacity
90ºC
in Air
AWG
or
KCMIL
mils No. mils in in in in lb/MFT in Amps Amps
4 115 3 10 0.226 0.5 0.56 1.42 929 10 80 81
2 115 3 10 0.284 0.56 0.62 1.55 1095 11 105 110
1 115 3 10 0.324 0.6 0.66 1.64 1200 12 120 125
1/0 115 3 10 0.364 0.64 0.7 1.78 1429 13 140 145
2/0 115 3 8 0.408 0.69 0.74 1.88 1645 14 160 170
3/0 115 3 8 0.458 0.74 0.79 1.99 1834 14 180 195
4/0 115 3 8 0.515 0.79 0.85 2.11 2066 15 205 225
250 115 3 8 0.561 0.85 0.9 2.22 2273 16 230 250
350 115 3 7 0.664 0.95 1 2.44 2797 18 280 310
500 115 3 6 0.794 1.08 1.15 2.76 3595 20 340 385
750 115 3 5 0.974 1.27 1.34 3.22 4955 23 425 495
1000 115 3 4 1.124 1.42 1.49 3.55 6103 25 495 585