IEC 60502-1 NA2XRH 0.6/1kV XLPE LSZH SWA LSZH Cable Aluminium

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

Where there is a risk of fire, NA2XRH XLPE SWA LSZH Cable is utilized in refineries, hotels, schools, tunnels, high buildings, hospitals, power plants, data processing centers, and populous commercial areas.

Performance

Electrical performance U0/U:
0.6/1kV

Chemical performance:
chemical, UV&oil resistance

Mechanical performance:
minimum bending radius:15 x overall diameter

Terminal performance:
Fixed: -5°C to +90°C

Fire performance:
-Flame Retardant in accordance with Standard IEC/EN 60332-1-2 and IEC/EN 60332-3-24
Low Smoke Zero Halogen as per IEC/EN 60754-1/2 and IEC/EN 61034-1/2 Standards

Constructions

Conductor:
stranded class 2 aluminum conductor

Insulation:
XLPE (Cross-linked polyethylene)

Filler:
LSZH (Low Smoke Zero Halogen)

Armoring:
SWA(Galvanized round steel wire)

Sheath:
LSZH (Low Smoke Zero Halogen)

Core Identification:
Two cores: Blue Brown
Three cores:brown,black,gray
Four cores:brown,black ,gray,blue
Five cores:brown,black,gray,black,blue

Sheath Colour:
black

IEC 60502-1 NA2XRH 0.61kV XLPE LSZH SWA LSZH Cable Aluminium  (2)

1.Conductor
2.Insulation
3.Filler
4.Armour
5.Sheath

Cable Marking and Packing Materials

Cable Marking:
printing, embossing ,engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Specifications

- IEC 60502-1, EN 50267-2-1, EN 60228 Standard

Physical Performance and Resistance

NO. OF CORES NOMINAL CROSS SECTIONAL AREA NOMINAL OVERALL DIAMETER NOMINAL WEIGHT MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C
- mm2  mm kg/km ohms/km
4 25 29.1 1643 1.2
4 35 32.2 1970 0.868
4 50 37.7 2754 0.641
4 70 43 3696 0.443
4 95 48.2 4546 0.32
4 120 52.2 5264 0.253
4 150 57.7 6289 0.206
4 185 66.9 8596 0.164
4 240 74 10334 0.125
5 16 25.3 1314 1.94
5 25 31.9 1923 1.2
5 35 36.1 2547 0.868
5 50 42.3 3576 0.641
5 70 47.5 4388 0.443
5 95 54.1 5575 0.32

Electrical Performance

NOMINAL CROSS SECTIONAL AREA CURRENT CARRYING CAPACITY
In Ground In Air
 mm2  Amps  Amps
25 90 97
35 112 120
50 136 146
70 174 187
95 211 227
120 245 263
150 283 304
185 323 347
240 382 409
16 90 77
25 112 97
35 136 120
50 174 146
70 211 187
95 245 227

Any questions for us?