AEIC CS8 5-35kV Copper AIA Interlocked Armored Cable Metal Clad Cable

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

AIA Interlocked Armored Cable offers an economical, rugged and reliable alternative to labor-intensive cable in conduit wiring methods Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced not more than six feet apart Installed in both exposed and concealed work, wet or dry locations, directly buried or embedded in concrete.

Construction

Conductor:
Class A or B Compressed concentric stranded copper conductor. Optional water-blocking.

Conductor Shield:
Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation

Insulation:
Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649

Insulation Shield:
Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.

Metallic Shield:
The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap

Ground Wire:
Three bare copper ground wires placed at the interstice of the conductor.

Fillers:
Non hygroscopic fillers, forming a firm and cylindrical cable core.

Binder Tape:
A binder tape is applied to maintain core symmetry and mechanical stability.

Armor:
Aluminum Interlocked Armor applied over the binder tape of the cable core

Jacket:
Black, sunlight resistant, flame retardant PVC jacket

AEIC CS8 5-35kV Copper AIA Interlocked Armored Cable Metal Clad Cable (2)

1. Conductor
2. Conductor Shield
3. Insulation
4. Insulation Shield
5. Copper Tape Shied

6. Ground Conductor
7. Filler
8. Binder
9. AIA Armour
10. Overall Jacket

Cable Marking and Packing Materials

Cable Marking:
printing, embossing ,engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Specifications

- AEIC CS8, Specifications for Shielded Power Cable, 5-46kV
- ICEA S-93-639, 5-46 kV Shielded Power Cable
- ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
- UL-1072 MV-105

- UL-1569, Metal Clad Cables
- IEEE 383 Flame Test
- For 105°C continuous, 140°C emergency, 250°C short-circuit operation.
- UL MC-HL available upon request

AEIC CS8 5-35kV copper Conductor AIA Interlocked Armored Cable Specification

Size Insulation
Thickness
Ground
Wires
Size of
Ground
Wires
Conductor
Diameter
Insulation
Diameter
Insulation
Shield
Diameter
Overall
Jacket
Diameter
Approximate
Weight
Minimum
Bending
Radius
Ampacity
105ºC
in
Duct
Ampacity
105ºC
in
Air
AWG / KCMIL (mil) No. AWG in in in in lb/MFT in - -
4 90 3 10 0.215 0.45 0.51 1.47 1265 11 110 115
2 90 3 10 0.266 0.5 0.56 1.58 1585 12 145 154
1 90 3 8 0.299 0.53 0.59 1.68 1829 12 165 180
1/0 90 3 8 0.341 0.57 0.63 1.77 2111 13 190 205
2/0 90 3 8 0.376 0.61 0.67 1.86 2540 14 220 240
3/0 90 3 7 0.423 0.66 0.71 1.96 2951 14 250 280
4/0 90 3 7 0.479 0.71 0.77 2.08 3458 15 285 320
250 90 3 7 0.522 0.76 0.82 2.19 3914 16 315 355
350 90 3 6 0.622 0.86 0.92 2.44 5146 18 380 440
500 90 3 5 0.742 0.98 1.05 2.73 6898 20 460 545
750 90 3 4 0.917 1.16 1.24 3.14 9832 23 570 685
1000 90 3 4 1.071 1.32 1.39 3.48 12524 25 645 790