DIN VDE 0276 0.6/1 kV NAY2Y-J NAY2Y Cable AL/PVC/HDPE

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

NAY2Y-J NAY2Y cable is intended for fixed installations in indoor, outdoor installations, in soil, water and concrete, if no rear mechanical damage is expected.
The NAY2Y power cable should only be installed by trained and qualified electrical engineering personnel.product design
According to recognized standards. Applicable installation regulations must always be observed.

Meaning of Abbreviations

NA= Aluminium conductor
Y= PVC insulation
2Y= HDPE sheath

Conductor abbreviations "re", "rm", "se", "sm":
r = round conductor form;
s = sectorial conductor form;
e = single-wire conductor;
m = multi-wire conductor;

Performance

Voltage Rating:
Uo/U (Um) 0.6/1 (1.2)kV

Test Voltage:
4kV

Temperature Rating:
Operating temperature: -30℃ to +70℃, Maximum conductor temperature: 70℃

Maximum Short Circuit Temperature:
+160°C (max 5 seconds)

Minimum Bend Radius:
Single core: 15 x overall diameter
Multi core: 12 x overall diameter

Fire Performance:
Flame-retardant according IEC 60332-1-2

Construction

Conductor:
RE: Class 1 round solid aluminium
SE: Class 1 sector shaped solid aluminium
RM: Class 2 round stranded aluminium
SM: Class 2 sector shaped stranded aluminium

Insulation:
PVC (Polyvinyl Chloride)

Bedding:
PVC

Sheath:
HDPE (High-density polyethylene)

Core Identification
1 core: Black
3 core + earth: Green/Yellow Blue Brown
4 core: Green/Yellow Brown Black Grey
5 core: Green/Yellow Blue Brown Black Grey

Sheath Colour:
Black

NAY2Y NAY2Y-j (2)

1.Aluminium Conductor
2.PVC Insulation

3.PVC Bedding
4.HDPE Sheath

Cable Marking and Packing Materials

Cable Marking:
printing, embossing, engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Specifications

VDE 0276-603, VDE 0276-627, HD 603 S1, HD 627 S1, IEC 60502-1

0.6/1kV NAY2Y Cable Specification

Number of cores, nominal cross cectional area Conductor shape Maximum resistance of conductor at 20⁰C Overall diameter (approx.) Rated current-carrying capacity in earth Rated current-carrying capacity in air Total net weight(approx.)
Number x mm² Shape Ω/km mm A A kg/km
1×16 RM 1.91 11.5 - - 132
1×25 RM 1.2 12.8 160 110 162
1×35 RM 0.868 13.7 193 135 211
1×50 RM 0.641 15 230 166 255
1×70 RM 0.443 16.8 283 210 343
1×95 RM 0.32 18.8 340 259 468
1×120 RM 0.253 20 389 302 537
1×150 RM 0.206 21.9 436 345 638
1×185 RM 0.164 24.8 496 401 780
1×240 RM 0.125 27.8 578 479 989
1×300 RM 0.1 30.2 656 555 1233
1×400 RM 0.0778 33.8 756 653 1534
4×16 RM 1.91 22 - - 602
4×25 RM 1.2 25.6 102 82 704
4×35 RM 0.868 29.8 123 100 832
4×35 SM 0.868 28 123 100 797
4×50 SM 0.641 31 144 119 1004
4×70 SM 0.443 35.7 179 152 1415
4×95 SM 0.32 39 215 186 1855
4×120 SM 0.253 43.8 245 216 2145
4×150 SM 0.206 46.8 275 246 2711
4×185 SM 0.164 50.8 313 285 3287
4×240 SM 0.125 55.8 364 338 4158
4×16+1.5 RM+RE 1.91/12.1 22 - - 617
4×25+1.5 RM+RE 1.20/12.1 25.6 102 82 719
4×35+1.5 RM+RE 0.868/12.1 29.8 123 100 847
4×35+1.5 SM+RE 0.868/12.1 28 123 100 812
4×50+1.5 SM+RE 0.641/12.1 31 144 119 1019
4×70+1.5 SM+RE 0.443/12.1 35.7 179 152 1430
4×95+1.5 SM+RE 0.320/12.1 39 215 186 1875
4×120+1.5 SM+RE 0.253/12.1 43.8 245 216 2165
4×150+1.5 SM+RE 0.206/12.1 46.8 275 246 2731
4×185+1.5 SM+RE 0.164/12.1 50.8 313 285 3307
4×240+1.5 SM+RE 0.125/12.1 55.8 364 338 4178

Any questions for us?

For inquiries about our products or price list , please leave your email to us and we will be in touch within 24 hour