Mineral Insulated Copper Clad Cable is a cable with a copper conductor core wrapped in a copper sheath and magnesium oxide powder as an inorganic insulating material to isolate the conductor and sheath. The mineral cable can become MICC cable or MI cable (Mineral Insulated Cable). MICC cable is Suitable for fire protection applications such as alarm circuits, fire pumps and sprinklers, smoke control systems and emergency power & emergency lighting. Also used in process industries where flamable liquids or gases are present.

Performance

Voltage Rating (Uo/U):
0.6/1KV. 300/500v for light duty use, 450/750v for heavy duty use.

Temperature Rating:
Fixed: -15°C to +70°C
Flexed: -5°C to +50°C

Minimum Bending Radius:
Fixed: 12 x overall diameter

Core Identification:
Up to and including 5 core: colour coded or number coded
7 core and above: number coded

Construction

Conductor:
The conductor is made of the first high-quality annealed copper

Insulation layer:
high temperature resistant, non-combustible inorganic magnesium oxide powder

Metal sheath:
Use high-quality annealed copper as the sheath.
An outer protective layer (optional): when there are requirements for corrosion protection, identification, or aesthetics, a plastic coat can be used (a halogen-free low-smoke coat is recommended).

BS6387-MICC-Mineral-Insulated-Copper-Clad-Cable-(2)

1. Annealed copper conductor
2. Mineral Insulation

3. Copper Sheath
4. Outer Sheath(Optional)

Cable Marking and Packing Materials

Cable Marking:
printing, embossing, engraving

Packaging:
wooden drum, steel drum, steel-wooden drum

Specifications

BS6387 C-W-Z BS EN 60702 Part 1 standard

Mechanical Performance

Light Duty 0.5KV
NO. OF CORES & NOMINAL CONDUCTOR CROSS SECTIONAL AREA CROSS SECTIONAL AREA OF COPPER SHEATH NOMINAL OVERALL DIAMETER NOMINAL WEIGHT
WITH LSZH COVERING WITHOUT LSZH COVERING WITH LSZH COVERING WITHOUT LSZH COVERING
NO.×MM² MM² MM MM KG/KM KG/KM
2×1.0 5.4 6.4 5.1 126 104
2×1.5 6.3 7 5.7 154 136
2×2.5 8.2 7.9 6.6 206 187
2×4.0 10.7 9.2 7.7 322 248
3×1.0 6.7 7.1 5.8 159 136
3×1.5 7.8 7.7 6.4 194 176
3×2.5 9.5 8.8 7.3 272 223
4×1.0 7.7 7.6 6.3 187 162
4×1.5 9.1 8.3 7 231 203
4×2.5 11.3 9.6 8.1 336 277
7×1.0 11 9.3 7.6 269 236
7×1.5 11.8 9.9 8.4 351 295
7×2.5 15.4 11.2 9.7 475 411
Heavy Duty 0.75KV
NO. OF CORES &  NOMINAL CONDUCTOR CROSS SECTIONAL AREA CROSS SECTIONAL AREA OF COPPER SHEATH NOMINAL OVERALL DIAMETER NOMINAL WEIGHT
WITH LSZH COVERING WITHOUT LSZH COVERING WITH LSZH COVERING WITHOUT LSZH COVERING
NO×MM² MM² MM MM KG/KM KG/KM
1×6.0 8 7.7 6.2 213 173
1×10.0 9 8.8 7.3 273 240
1×16.0 12 9.8 8.3 361 326
1×25.0 15 11.1 9.6 506 457
1×35.0 18 12.2 10.7 650 585
1×50.0 22 13.6 12.1 842 758
1×70.0 27 15.2 13.7 1147 1016
1×95.0 32 17.4 15.4 1520 1324
1×120.0 37 18.8 16.8 1870 1612
1×150.0 44 20.4 18.4 2230 1949
1×185.0 54 23.2 20.4 2575 2370
1×240.0 70 26.1 23.3 3312 3050
1×300.0 79 28.8 26 3972 3791
1×400.0 91 32.8 30 5211 5004
2×1.5 11 9.4 7.9 259 237
2×2.5 13 10.2 8.7 314 276
2×4.0 16 11.3 9.8 398 355
2×6.0 18 12.4 10.9 483 446
2×10.0 24 14.2 12.7 697 619
2×16.0 30 16.2 14.7 968 850
2×25.0 38 19.1 17.1 1275 1178
3×1.5 12 9.8 8.3 290 254
3×2.5 14 10.8 9.3 365 323
3×4 17 11.9 10.4 461 415
3×6 20 13 11.5 590 526
3×10 27 15.1 13.6 853 754
3×16 34 17.1 15.6 1080 1034
3×25 42 20.2 18.2 1548 1444
4×1.54 14 10.6 9.1 344 305
4×2.5 16 11.6 10.1 430 384
4×4 20 12.9 11.4 577 507
4×6 24 14.2 12.7 718 644
4×14×160 30 16.3 14.8 1050 911
4×16 39 19.3 17.3 1390 1286
4×25 49 22.3 20.1 1943 1805
7×1.5 18 12.3 10.8 478 432
7×2.5 22 13.6 12.1 614 559
12×1.555 28 15.8 14.1 772 712
12×2.5 34 17.9 15.6 970 911
19×1.5 37 18.9 16.6 1086 992

Electrical Performance

Light Duty 0.5KV
NOMINAL CONDUCTOR DIAMETER MM 1.13 1.39 1.77 2.25
NOMINAL CONDUCTOR CROSS SECTION MM² 1 1.5 2.5 4
MAXIMUM DC CONDUCTOR RESISTANCE Ω/KM 18.1 12.1 7.41 4.61
VOLTAGE RATING KV 0.5
Heavy Duty 0.75KV
NOMINAL CONDUCTOR DIAMETER MM 1.39 1.77 2.25 2.75 3.57 4.5 5.66 6.66 7.75
NOMINAL CONDUCTOR CROSS SECTION MM² 1.5 2.5 4 6 10 16 25 35 50
MAXIMUM DC CONDUCTOR RESISTANCE Ω/KM 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387
VOLTAGE RATING KV 0.75
NOMINAL CONDUCTOR DIAMETER MM 9.32 10.98 12.33 13.7 15.18 17.33 19.37 22.37
NOMINAL CONDUCTOR CROSS SECTION MM² 70 95 120 150 185 240 300 400
MAXIMUM DC CONDUCTOR RESISTANCE Ω/KM 0.268 0.193 0.153 0.124 0.101 0.0775 0.0601 0.047
VOLTAGE RATING KV 0.75