BS 6724 1.9/3.3kV Single Core AWA Armoured Cable LSZH

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

1.9/3.3kV Single Core AWA Armoured Cable for use in power networks, underground, outdoor and indoor applications and for use in cable ducting. For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment.

Performance

Electrical performance Uo/U:
1.9/3.3kV

Chemical performance:
chemical, UV&oil resistance

Mechanical performance:
minimum bending radius:15 x overall diameter

Terminal performance:
-Maximum service temperature:90℃
-Maximum short-circuit temperature: 250℃(Max.5s)

Fire performance:
Low Smoke Zero Halogen according to IEC/EN 61034, IEC/EN 60754
Flame retardant according to IEC/EN 60332-1

Constructions

Conductor:
class 2 stranded copper conductor

Insulation:
XLPE (Cross-linked polyethylene)

Filler:
HFFR (Halogen free flame retardant)

Armoring:
AWA (Aluminium Wire Armour)

Sheath:
HFFR (Halogen free flame retardant)

Core Identification:
Brown

Sheath Color:
black

BS 6724 1.93.3kV Single Core AWA Armoured Cable LSZH (2)

Cable Marking and Packing Materials

Cable Marking:
printing, embossing ,engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Specifications

BS 6724, Standard

BS 6724 1.9/3.3kV Single Core AWA Armoured Cable Size Chart Physical Performance

NO. OF CORES NOMINAL CROSS SECTIONAL AREA NOMINAL DIAMETER OF CONDUCTOR NOMINAL THICKNESS OF INSULATION MINMUM THICKNESS OF OUTER SHEATH NOMINAL OUTER DIAMETER NOMINAL  WEIGHT MAXIMUM CONDUCTER DC RESISTANCE AT 20°C
- mm2 mm  mm  mm mm kg/km Ω/km
1 50 8.1 2 1.08 19 956 0.387
1 70 9.7 2 1.08 20 1201 0.268
1 95 11.4 2 1.08 22 1499 0.193
1 120 12.65 2 1.16 25 1936 0.153
1 150 14.15 2 1.16 26 2254 0.124
1 185 15.75 2 1.24 28 2650 0.0991
1 240 18.2 2 1.24 30 3280 0.0754
1 300 20.5 2 1.32 33 3938 0.0601
1 400 23 2 1.4 37 5090 0.0471
1 500 26 2.2 1.48 40 6255 0.0366
1 630 29.7 2.4 1.56 45 7809 0.0283

Electrical Performance(Current Carrying Capacity of copper conductor )

NOMINAL  CROSS  SECTIONAL  AREA REFERENCE METHOD C (CLIPPED DIRECT) REFERENCE METHOD F (IN FREE AIR OR ON A PERFORATED CABLE TRAY ETC HORIZONTAL OR VERTICAL ETC)
Touching Touching Spaced by one diameter
Three Cables Single-Phase AC or DC flat Three or Four Cables Three-Phase AC Two Cables Single Phase AC or DC flat Three Cables Three Phase AC flat Three Cables Three-Phase AC trefoil Two Cables DC Two Cables single-phase AC Three or Four Cables Three-phase AC
Horizontal Vertical Horizontal Vertical Horizontal Vertical
mm2 Amps  Amps  Amps  Amps  Amps  Amps  Amps  Amps  Amps  Amps  Amps
50 237 220 253 232 222 284 270 282 266 288 266
70 303 277 322 293 285 356 349 357 337 358 331
95 367 333 389 352 346 446 426 436 412 425 393
120 425 383 449 405 402 519 497 504 477 485 449
150 488 437 516 462 463 600 575 566 539 549 510
185 557 496 587 524 529 688 660 643 614 618 574
240 656 579 689 612 625 815 782 749 714 715 666
300 755 662 792 700 720 943 906 842 805 810 755
400 853 717 899 767 815 1137 1094 929 889 848 797
500 962 791 1016 851 918 1314 1266 1032 989 923 871
630 1082 861 1146 935 1027 1528 1474 1139 1092 992 940

Any questions for us?

For inquiries about our products or price list , please leave your email to us and we will be in touch within 24 hour