Super Thermal Alloy Conductor Invar Reinforced STACIR Conductor

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

One new kind of overhead conductor is the STACIR/AW conductor.By using trapezoidal wire, the conductor's cross sectional area is increased, which has the effect of raising the conductor's conductive capacity.
Applications involving re-conductoring are suitable for STACIR/AW conductors. Without altering the tower, the current conductor can be swapped out to increase the capacity of the transmission line.

Advantages

The INVAR core and outer layer have their own knee points at the installation temperature. Reduce the sag as the temperature rises.

The conductor's mechanical strength is preserved by the thermal expansion coefficient associated with the INVAR core above the knee point, and the constant operating temperature is up to 210°C. This method calls for an experienced installation stage.
It is suitable for ACSR replacement on flat land or with small level differences.

Construction

The outer layers of the Super Thermal Alloy Conductor Invar Reinforced (STACIR) conductor are made of Super Thermal Aluminium (STAL) alloy wires, which have a maximum operating temperature of 210°C (410°F). INVAR wires covered in aluminum make up the inner core. The metal alloy INVAR has 36% nickel in steel.

Packing

Delivery lengths are determined from a consideration of such factors as physical drum dimensions, drum weights, span length, handling equipment or the customer’s request.

Packing Materials

Wooden drum,steel-wooden drum,steel drum.

asd (2)

Specifications

IEC 62004: Super Thermal-resistant aluminium alloy wire for overhead line conductor

IEC 61089: Round wire concentric lay overhead electrical stranded conductors

IEC 1232: Aluminium-clad steel wires for electrical purposes

PROPERTIES STACIR (ACSR MOOSE EQUIVALENT) STACIR ( ACSR ZEBRA EQUIVALENT) STACIR (ACSR PANTHER EQUIVALENT)
Typical factors 3.53 mm 0.1390 in 3.18 mm 0.1252 in 3.00 mm 0.1181 in
Reference specifications IEC 62004 IEC 62004 IEC 62004
Total cross section area 597.00 mm2 0.9254 in2 484.50 mm2 0.751 in2 261.50 mm2 0.4054 in2
Conductive wire Al Zr AT3 Al Zr AT3 Al Zr AT1
Core wire Aluminium clad Invar Aluminium clad Invar Aluminium clad Invar
Conductor diameter 31.77mm 1.2508 in 28.62 mm 1.1268 in 21.00 mm 0.8268 in
Weight 1993 kg/km 1339.2 lbs/mile 1582 kg/km 1063.1 lbs/mile 939 kg/km 631 lbs/mile
Ultimate tensile strength 14641 kg 32277.84 lbs 11968 kg 26384.89 lbs 8436 kg 18598.17 lbs
DC resistance at 20°C temperature 0.06 Ω/km 0.09Ω /mile 0.07Ω /km 0.11Ω /mile 0.13 Ω/km 0.21Ω /mile
Maximum operating temperature 210°C 410°F 210°C 410°F 210°C 410°F
Current carrying capacity at maximum operating temperature 1871 Amp 1626 Amp 1040 Amp