BS 6724 0.6/1kV Single Core AWA LSZH Power Cable

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

XLPE insulated low smoke zero halogen (LSZH) power cables are also known as 0.6/1kV Single Core AWA LSZH Power Cables.
In residential, commercial, or industrial facilities, such as factories, power plants, subways, underground tunnels, and high-rise structures, etc., they are utilized in the power supply of lighting and power circuits. Fit for fixed installations in both indoor and outdoor settings, including cable trays, tunnels, conduits, etc.

Performance

Voltage Rating:
Uo/U 0.6/1kV

Temperature Rating:
Fixed: -20°C to +90°C

Minimum Bending Radius:
Fixed: 6 x overall diameter

Terminal performance:
-Maximum service temperature: 90℃
-Maximum short-circuit temperature: 250℃(Max.5s)
-Minimum service temperature: -10℃

Fire performance:
Low Smoke Zero Halogen according to IEC/EN 60754-1/2, IEC/EN 61034-2
Flame Retardant: according to IEC/EN 60332-1-2, IEC/EN 60332-3-24 Cat C

Constructions

Conductor:
Circular stranded aluminum conductor or class 2 stranded copper conductor

Insulation:
XLPE (Cross-linked polyethylene)

Bedding:
LSZH (Low Smoke Zero Halogen)

Armoring:
AWA (Aluminium Wire Armour)

Sheath:
LSZH (Low Smoke Zero Halogen)

Core Identification:
Brown

Sheath Colour:
black

BS 6724 0.61kV Single Core AWA LSZH Power Cable  (2)

Cable Marking and Packing Materials

Cable Marking:
printing, embossing ,engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Specifications

BS 6724, IEC/EN 60502-1, EN 60228 standard

BS 6724 0.6/1kV Single Core AWA LSZH Power Cable Specification Physical Performance and Resistance

NO. OF CORES NOMINAL CROSS SECTIONAL AREA NOMINAL THICKNESS OF INSULATION MINIMUM NO. OF WIRES IN CONDUCTOR MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC
Circular Circular Compact Shaped
Copper Aluminum Copper Aluminum Copper Aluminum Copper Aluminum
- mm2  mm - - - - kg/km kg/km Ω/km Ω/km
1 50 1 19 19 6 6 6 6 0.387 0.641
1 70 1.1 19 19 12 12 12 12 0.268 0.443
1 95 1.1 19 19 15 15 15 15 0.193 0.32
1 120 1.2 37 37 18 18 18 18 0.153 0.253
1 150 1.4 37 37 18 15 18 15 0.124 0.206
1 185 1.6 37 37 18 15 18 15 0.0991 0.164
1 240 1.7 37 37 34 30 34 30 0.0754 0.125
1 300 1.8 61 61 34 30 34 30 0.0601 0.1
1 400 2 61 61 53 53 53 53 0.047 0.0778
1 500 2.2 91 91 53 53 53 53 0.475 0.0605
1 630 2.4 91 91 53 53 53 53 0.0283 0.0469
1 800 2.6 91 91 53 53 - - 0.0221 -
1 1000 2.8 91 91 53 53 - 0.0176 -

Electrical Performance(Current Carrying Capacity of copper conductor )

NOMINAL CROSS SECTIONAL AREA REFERENCE METHOD C (CLIPPED DIRECT) REFERENCE METHOD F  (IN FREE AIR OR ON A PERFORATED CABLE TRAY, HORIZONTAL OR VERTICAL)
TOUCHING TOUCHING SPACED BY ONE CABLE DIAMETER
Two Cables Single Phase AC or DC Flat Three or Four Cables Three Phase AC Flat Three Cables Single-Phase AC or DC Flat Three Cables Three-Phase AC Flat Three Cables Three-Phase AC Trefoil Two Cables DC Two Cables Single Phase AC Three or Four Cables Three-Phase AC
Horizontal Vertical Horizontal Vertical Horizontal Vertical
mm2 Amps Amps Amps Amps Amps Amps Amps Amps Amps Amps Amps
50 237 220 253 232 222 284 270 282 266 288 266
70 303 277 322 293 285 356 349 357 337 358 331
95 367 333 389 352 346 446 426 436 412 425 393
120 425 383 449 405 402 519 497 504 477 485 449
150 488 437 516 462 463 600 575 566 539 549 510
185 557 496 587 524 529 688 660 643 614 618 574
240 656 579 689 612 625 815 782 749 714 715 666
300 755 662 792 700 720 943 906 842 805 810 755
400 853 717 899 767 815 1137 1094 929 889 848 797
500 962 791 1016 851 918 1314 1266 1032 989 923 871
630 1082 861 1146 935 1027 1528 1474 1139 1092 992 940
800 1170 904 1246 987 1119 1809 1744 1204 1155 1042 978
1000 1261 961 1345 1055 1214 2100 2026 1289 1238 1110 1041