BS 7870 Aluminium Split PVC Concentric Wire DNO Supply Cable

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

Distribution network operators (DNOs) employ PVC jacketed concentric neutral wire to make the final connection to residential homes.
Concentric Wire is Additionally useful for sub main distribution, specifically in high-rise structures and street lighting systems.

Performance

Electrical performance U0/U:
0.6/1kV

Mechanical performance:
minimum bending radius:8 x overall diameter

Terminal performance:
-Maximum service temperature:70℃
-Minimum service temperature:-15℃

Fire performance:
-Flame Retardant according to IEC/EN 60332-1-2 Standard

Construction

Conductor:
Class 2 solid Al conductor

Insulation:
XLPE

Neutral Conductor:
Plain copper wires covered by a blue polymeric compound

Earth Continuity Conductor:
Plain copper wires

String Separator:
Non-hydroscopic separator

Sheath:
PVC

Sheath Colour:
black

Cable Marking and Packing Materials

Cable Marking:
printing, embossing, engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Specifications

- BS 7870-3-21, EN 60228 Standard

Physical Performance Parameters

NO. OF
CORES
NOMINAL CROSS SECTIONAL AREA NOMINAL OVERALL DIAMETER MAXIMUM DC RESISTANCE OF CONCENTRIC CONDUCTOR AT 20°C
Phase Neutra Earth
- mm2 mm ohms/km ohms/km ohms/km
1 25 15 1.2 1.2 1.2
1 35 16 0.868 0.76 1.2
3 25 23.5 1.2 1.2 1.2
3 35 26 0.868 0.76 1.2

Electrical Performance Parameters

NO. OF
CORES
NOMINAL CROSS
SECTIONAL AREA
SPLIT CONCENTRIC CABLE CURRENT CARRYING CAPACITY
In Air Clipped Direct Enclosed in Conduit on a Wall
- mm2 Amps Amps Amps
1 25 127 119 105
1 35 158 147 128
3 25 97 90 84
3 35 120 112 103