AEIC CS8 5-35kV Copper AIA Interlocked Metal Cable Cable

CATEGORY DOWNLOAD SPECIFICATIONS

Product Details

Product parametri

Applicationem

AIA Interlocked Cable cataphractos offert oeconomicum, asperum et certum jocus ad funem intensivum laboris in ductum wiring methodi insertas eculeis metallicis, canalibus, in curriculis, in cables scutulis vel munitis ad subsidia non plus quam sex pedes inauguratis in utroque exposito et inaugurato. opus occultum, locis humidis vel siccis, protinus in concreto obrutis vel immersis.

Construction

Conductor:
Classis A vel B Concentrici destitutus aeris conductor Cogo.Libitum aquarum consequat.

Conductor clypeus:
Clypeus thermosetting semiconducting extructus, qui liberam a conductore spoliavit et cum insulatione religata est.

Insulatio:
Extrusa, vacua Lignum-Retardant Crucis-coniunctum Polyethylene (TRXLPE) definitum in ANSI/ICEA S-94-649

Nulla scutum:
Clypeus thermosetting semiconductus extruditur cum adhaesione moderata ad insaltationem comparatam debitam aequilibrium inter integritatem electricam et facilitatem nudandi.

Scutum metallicum:
Clypeus metallicus planus est uncoated 5-mil crassus taeniola cuprea helice applicata cum minimum 20% overlap

Humus Wire:
Tria fila aenea nuda humo interstitium conductoris posuerat.

Fillers:
Non fillers hygroscopicus, firmum et cylindricum nucleum formans.

Tape ligans:
Ligans taeniola ad nucleum symmetriam et mechanicam stabilitatem applicatur.

Armor:
Aluminium interlocked armatura super ligans taenia dilabi nucleo applicata

Jacket:
Niger, solis renitens, flamma retardat PVC jacket

AEIC CS8 5-35kV Copper AIA Interlocked Metal Cable Clad Cable (2)

1. Conductor
2. Conductor clypeus
3. Insulation
4. Insulation Scutum
5. Aeris Tape Shied

6. Terrae conductor
7. Filler
8. Seneca
9. AIA Armor
10. Super Jacket

Cable Vestigium et sarcina Materials

Cable Vestigium:
impressio, impressio, sculptura

Materias stipare:
lignea orum, chalybea tympanum, chalybe-ligneus

Specifications

- AEIC CS8, Specificationes pro Shielded Power Cable, 5-46kV
- ICEA S-93-639, 5-46 kV Shielded Power Cable
- ICEA S-97-682, Utilitas Shielded Power Cable Rated 5-46 kV
- UL-1072 MV-105 .

- UL-1569, Metallum Cables
- IEEE 383 Flamma Test
- Pro continuum 105°C, subitis 140°C, operatio brevis 250°C.
- MC-HL praesto ad petitionem

AEIC CS8 5-35kV aeris Conductor AIA Interlocked Cables Specification

Magnitudo Insulation
Crassitudo
Humus
filis
Magnitudo of
Humus
filis
Conductor
Diameter
Insulation
Diameter
Insulation
Scutum
Diameter
Super
Jacket
Diameter
Proxime
Pondus
Minimum
curvus
Radius
Ampacity
105ºC
in
Duct
Ampacity
105ºC
in
Air
AWG / KCMIL (mil) Nec. AWG in in in in lb/MFT in - -
4 90 3 10 0.215 0.45 0.51 1.47 1265 11 110 115
2 90 3 10 0.266 0.5 0.56 1.58 1585 12 145 154
1 90 3 8 0.299 0.53 0.59 1.68 1829 12 165 180
1/0 90 3 8 0.341 0.57 0.63 1.77 2111 13 190 205
2/0 90 3 8 0.376 0.61 0.67 1.86 2540 14 220 240
3/0 90 3 7 0.423 0.66 0.71 1.96 2951 14 250 280
4/0 90 3 7 0.479 0.71 0.77 2.08 3458 15 285 320
250 90 3 7 0.522 0.76 0.82 2.19 3914 16 315 355
350 90 3 6 0.622 0.86 0.92 2.44 5146 18 380 440
500 90 3 5 0.124 0.98 1.05 2.73 6898 20 460 545
750 90 3 4 0.917 1.16 1.24 3.14 9832 23 570 685
1000 90 3 4 1.071 1.32 1.39 3.48 12524 25 645 790

Quaere nobis?