AS/NZS 5000.1 0.6/1kV SWA PVC Multicore Cable 2C+E 3C+E 4C+E Orange Circular

I-DOWNLOAD ANG MGA ESPISIPIKASYON NG KATEGORYA

detalye ng Produkto

Parameter ng produkto

Aplikasyon

Ang 0.6/1kV PVC Multicore Cable na ito ay angkop para sa AC 50HZ, at maaaring gamitin para sa Para sa mga Mains, Sub-mains at sub-circuits na hindi nakakulong, nakapaloob sa conduit na nakabaon nang direkta o underground ducts para sa mga gusali at industriyal na halaman kung saan hindi napapailalim sa mekanikal na pinsala.Angkop para sa glanding.

Pagganap

Pagganap ng kuryente U0/U:
0.6/1kV

Pagganap ng kemikal:
kemikal, UV at paglaban sa langis

Pagganap ng mekanikal:
minimum na radius ng baluktot: 15 x pangkalahatang diameter

Pagganap ng terminal:
- Pinakamataas na temperatura ng serbisyo: 90 ℃
-Maximum na short-circuit na temperatura: 250℃(Max.5s)
-Minimum na temperatura ng serbisyo:-10 ℃

Konstruksyon

Konduktor:
Plain annealed na tanso

pagkakabukod:
Polyvinyl chloride compound PVC V-90

Paglalagay:
Hindi hygroscopic na tagapuno

Bedding:
Polyvinyl chloride compound PVC 5V-90

Kulay ng kama:
Itim

nakasuot:
Galvanized Steel Wire(SWA)

Panlabas na Kaluban:
Polyvinyl chloride compound PVC 5V-90

Pangunahing Pagkakakilanlan:
2C + E - Pula, Itim, Berde/dilaw
3C + E – Pula, Puti, Asul, Berde/dilaw
4C + E - Pula, Puti, Asul, itim, Berde/dilaw

Kulay ng kaluban:
Kahel

0-6-1kV-Multicore-PVC-Insulated-PVC-Sheathed-Armored-Cables-(2)

1. Konduktor
2.Pagkabukod
3.Paglalatag

4. Kumot
5. Baluti
6. kaluban

Cable Marking at Mga Materyales sa Pag-iimpake

Pagmamarka ng Cable:
pagpi-print, embossing, ukit

Mga Materyales sa Pag-iimpake:
kahoy na tambol, bakal na tambol, bakal-kahoy na tambol

Mga pagtutukoy

-AS/NZS 5000.1 Standard
-AS/NZS 3008 Standard

-AS/NZS 1125 Standard
-SAA-173128-EA Standard

AS/NZS 5000.1 0.6/1kV 2C+E PVC Insulated PVC Sheathed Armored Cables Detalye

NOM.CONDUCTOR AREA CONDUCTOR NOM.kapal ng pagkakabukod NOM.LUGAR NG KONDUKTOR NG LUPA NOM.KAPAL NG INSULATION NG EARTH CONDUCTOR NOM.DIAMETER SA KAGA ARMOUR DIAMETER NOM.PANGKALAHATANG DYAMETRO TinatayangMISA
MM2 HINDI./ OD MM MM2 MM MM MM MM KG/KM
1.5 7/0.50 0.8 1.5 0.6 9 0.9 14.5 470
2.5 7/0.67 0.8 2.5 0.7 10 0.9 15.6 490
4 7/0.85 1 2.5 0.7 11.4 0.9 16.9 690
6 7/1.04 1 2.5 0.7 12.5 0.9 18 765
10 7/1.35 1 4 1 14.2 1.25 20.5 937
16 7/1.70 1 6 1 16.3 1.25 22.5 1295
25 7/2.14 1.2 6 1 20 1.6 27 1600
35 7/2.65 1.2 10 1 21.7 1.6 28.1 1775
50 19/1.89 1.4 16 1 24.7 1.6 31.3 2215
70 19/2.24 1.4 25 1.2 28.7 2 35.1 2880
95 19/2.65 1.6 25 1.2 32.6 2 40.4 3910

AS/NZS 5000.1 0.6/1kV 2C+E PVC Insulated PVC Sheathed Armored Cables Electrical Performance

CONDUCTOR MGA KASALUKUYANG RATING MGA KATANGIAN NG KURYENTE
NOMINAL NA LUGAR HINDI NAKAKAKITA SA HANGIN NILIBING DIREKTA NILIBING SA MGA DUCT MAXIMUM DC RESISTANCE @20°C MAXIMUM AC RESISTANCE @90℃ REACTANCE THREE PHASE VOLTAGE DROP @90℃
MM2 A A A OHM/KM OHM/KM OHM/KM MV/AM
1.5 18 28 22 13.6 16.5 0.111 33
2.5 26 40 31 7.41 9.01 0.102 18
4 34 52 40 4.61 5.61 0.102 11.2
6 44 65 51 3.08 3.75 0.0967 7.5
10 60 87 68 1.83 2.23 0.0906 4.46
16 80 115 88 1.15 1.4 0.0861 2.81
25 105 145 115 0.727 0.884 0.0853 1.78
35 130 180 140 0.524 0.638 0.0826 1.28
50 160 210 165 0.387 0.471 0.0797 0.957
70 200 260 205 0.268 0.327 0.077 0.673
95 250 310 250 0.193 0.236 0.0766 0.498

AS/NZS 5000.1 0.6/1kV 3C+E PVC Insulated PVC Sheathed Armored Cables Detalye

NOM.CONDUCTOR AREA CONDUCTOR NOM.kapal ng pagkakabukod NOM.LUGAR NG KONDUKTOR NG LUPA NOM.KAPAL NG INSULATION NG EARTH CONDUCTOR NOM.DIAMETER SA KAGA ARMOUR DIAMETER NOM.PANGKALAHATANG DYAMETRO TinatayangMISA
MM2 HINDI./ OD MM MM2 MM MM MM MM KG/KM
1.5 7/0.50 0.8 1.5 0.8 9.8 0.9 15.4 400
2.5 7/0.67 0.8 2.5 0.8 10.9 0.9 16.5 545
4 7/0.85 1 2.5 0.8 12.5 1.25 18.8 770
6 7/1.04 1 2.5 0.8 13.7 1.25 20 880
10 7/1.35 1 4 1 15.8 1.25 22.1 1160
16 7/1.70 1 6 1 18.1 1.6 25.1 1560
25 7/2.14 1.2 6 1 21.8 1.6 28.8 2100
35 7/2.65 1.2 10 1 23.8 1.6 30.3 2480
50 19/1.89 1.4 16 1 26.7 2 34.1 3140
70 19/2.24 1.4 25 1.2 31.4 2 39.8 4455
95 19/2.65 1.6 25 1.2 35.9 2.5 43.9 5520
120 19/2.94 1.6 35 1.2 39.5 2.5 47.5 6790
150 19/3.28 1.8 50 1.4 43.2 2.5 53.4 7970
185 37/2.65 2 70 1.4 48 2.5 58.7 9660
240 37/2.94 2.2 95 1.6 54.9 2.5 66 12330

AS/NZS 5000.1 0.6/1kV 3C+E PVC Insulated PVC Sheathed Armored Cables Electrical Performance

CONDUCTOR MGA KASALUKUYANG RATING MGA KATANGIAN NG KURYENTE
NOMINAL NA LUGAR HINDI NAKAKAKITA SA HANGIN NILIBING DIREKTA NILIBING SA MGA DUCT MAXIMUM DC RESISTANCE @20°C MAXIMUM AC RESISTANCE @90℃ REACTANCE THREE PHASE VOLTAGE DROP @90℃
MM2 A A A OHM/KM OHM/KM OHM/KM MV/AM
1.5 15 24 19 13.6 16.5 0.111 28.6
2.5 22 34 26 7.41 9.01 0.102 15.6
4 29 44 34 4.61 5.61 0.102 9.71
6 37 55 43 3.08 3.75 0.0967 6.49
10 51 74 57 1.83 2.23 0.0906 3.86
16 68 96 74 1.15 1.4 0.0861 2.43
25 91 125 96 0.727 0.884 0.0853 1.54
35 110 150 115 0.524 0.638 0.0826 1.11
50 135 180 140 0.387 0.471 0.0797 0.829
70 170 220 175 0.268 0.327 0.077 0.583
95 215 265 210 0.193 0.236 0.0766 0.431
120 245 300 240 0.153 0.188 0.0743 0.351
150 280 335 270 0.124 0.153 0.0745 0.296
185 325 380 310 0.0991 0.123 0.0744 0.251
240 385 440 370 0.0754 0.0955 0.0735 0.21

AS/NZS 5000.1 0.6/1kV 4C+E PVC Insulated PVC Sheathed Armored Cables Detalye

NOM.CONDUCTOR AREA CONDUCTOR NOM.kapal ng pagkakabukod NOM.LUGAR NG KONDUKTOR NG LUPA NOM.KAPAL NG INSULATION NG EARTH CONDUCTOR NOM.DIAMETER SA KAGA ARMOUR DIAMETER NOM.PANGKALAHATANG DYAMETRO TinatayangMISA
MM2 HINDI./ OD MM MM2 MM MM MM MM KG/KM
1.5 7/0.50 0.8 1.5 0.6 10.7 0.9 16.3 545
2.5 7/0.67 0.8 2.5 0.7 12 0.9 17.6 635
4 7/0.85 1 2.5 0.7 13.9 1.25 20.2 900
6 7/1.04 1 2.5 0.7 15.9 1.25 22.2 1050
10 7/1.35 1 4 1 17.5 1.6 24.5 1490
16 7/1.70 1 6 1 21.2 1.6 28.2 1810
25 7/2.14 1.2 6 1 24.4 1.6 32.2 2530
35 7/2.65 1.2 10 1 26.1 1.6 33.3 2990
50 19/1.89 1.4 16 1 30.4 2 38.8 4140
70 19/2.24 1.4 25 1.2 35.1 2 43.7 5470
95 19/2.65 1.6 25 1.2 39.6 2.5 49.6 7250
120 19/2.94 1.6 35 1.2 43.9 2.5 54.1 9090
150 19/3.28 1.8 50 1.4 48.5 2.5 59.1 9900
185 37/2.65 2 70 1.4 54.3 2.5 65.4 12110
240 37/2.94 2.2 95 1.6 61.6 3.15 74.7 16320

AS/NZS 5000.1 0.6/1kV 4C+E PVC Insulated PVC Sheathed Armored Cables Electrical Performance

CONDUCTOR MGA KASALUKUYANG RATING MGA KATANGIAN NG KURYENTE
NOMINAL NA LUGAR HINDI NAKAKAKITA SA HANGIN NILIBING DIREKTA NILIBING SA MGA DUCT MAXIMUM DC RESISTANCE @20°C MAXIMUM AC RESISTANCE @90℃ REACTANCE THREE PHASE VOLTAGE DROP @90℃
MM2 A A A OHM/KM OHM/KM OHM/KM MV/AM
1.5 15 24 19 13.6 16.5 0.111 28.6
2.5 22 34 26 7.41 9.01 0.102 15.6
4 29 44 34 4.61 5.61 0.102 9.71
6 37 55 43 3.08 3.75 0.0967 6.49
10 51 74 57 1.83 2.23 0.0906 3.86
16 68 96 74 1.15 1.4 0.0861 2.43
25 91 125 96 0.727 0.884 0.0853 1.54
35 110 150 115 0.524 0.638 0.0826 1.11
50 135 180 140 0.387 0.471 0.0797 0.829
70 170 220 175 0.268 0.327 0.077 0.583
95 215 265 210 0.193 0.236 0.0766 0.431
120 245 300 240 0.153 0.188 0.0743 0.351
150 280 335 270 0.124 0.153 0.0745 0.296
185 325 380 310 0.0991 0.123 0.0744 0.251
240 385 440 370 0.0754 0.0955 0.0735 0.21