BS 6622 3.8/6.6kV Copper Armoured Cable XLPE PVC

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

Medium voltage insulated 3.8/6.6kV Copper Armoured Cable cables are made for fixed wiring in ships and on mobile offshore units and can be used for power and control purposes.

Performance

Electrical performance U0/U:
3.8/6.6 (7.2) kV

Test Voltage (AC) :
15kV(CU)

Mechanical performance:
minimum bending radius:
Single core: 15x overall diameter
Multi core: 12 x overall diameter
(Single core 12 x overall diameter and 3 core 10 x overall diameter where bends are positioned adjacent to a joint or termination provided that the bending is carefully controlled by the use of a former)

Terminal performance :
-Maximum service temperature:90℃
-Maximum short-circuit temperature: 250℃(Max.5s)
-Minimum service temperature:-10℃

Fire performance:
-Flame Retardant according to IEC/EN 60332-1-2 Standard

Copper Armoured Cable Constructions

Conductor:
class 2 stranded compacted Cu conductor

Insulation:
Semi-conductive XLPE

Insulation Screen:
Semi-conductive XLPE

Metallic Screen:
Concentric copper wires and copper tape

Separator :
Binding tape

Inner Sheath:
PVC (Polyvinyl Chloride)

Armour:
Single core: AWA (Aluminium Wire)
Multi core: SWA (Galvanised steel wire)

Sheath:
PVC

Sheath Colour:
Red

BS 6622 3.86.6kV Copper Armoured Cable XLPE PVC (2)

1.Conductor
2.Conductor Screen
3.Insulation
4.Insulation Screen
5.Filler
6.Binding Tape

7.Metallic Screen
8.Binding Tape
9.Inner Sheath
10.Armour
11.Outer Sheath

Cable Marking and Packing Materials

Cable Marking:
printing, embossing ,engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Specifications

-BS 6622, IEC/EN 60228, IEC 60502-2 Standard

BS 6622 3.8/6.6kV Copper Armoured Cable Specification Physical Performance

NO. OF  CORES NOMINAL CROSS SECTIONAL AREA NOMINAL OVERALL DIAMETER NOMINAL  WEIGHT
- mm2 mm kg/km
1 35 24.3 1.023
1 50 25.5 1.171
1 70 27.3 1.418
1 95 29.2 1.719
1 120 31.1 2.013
1 150 32.3 2.386
1 185 35 2.866
1 240 37.7 3.486
1 300 41.7 4.256
1 400 47.1 5.406
1 500 51.9 6.693
1 630 55.8 8.212
3 50 48 4500
3 70 52 5500
3 95 56 6500
3 120 60 7500
3 150 63 8500
3 185 67 10000
3 240 74 13000
3 300 80 15500
3 400 89 19000

Electrical Performance(Current Carrying Capacity of copper conductor )

NO. OF CORES NOMINAL  CROSS  SECTIONAL  AREA MAXIMUM RESISTANCE OF CONDUCTOR AT 20°C OPERATING INDUCTANCE OPERATING  CAPACITY CONTINUOUS CURRENT RATING
In Ground at 20OC In Air at 30OC
Flat Trefoil Flat Trefoil Flat Trefoil
mm2 ohms/km mH/km mH/km uF/km Amps Amps Amps Amps
- 35 0.524 748 0.401 0.266 201 191 238 199
1 50 0.387 0.719 0.381 0.297 241 227 285 241
1 70 0.268 0.684 0.357 0.339 301 277 356 301
1 95 0.193 0.659 0.342 0.381 364 331 435 365
1 120 0.153 0.636 0.327 0.416 424 379 496 419
1 150 0.124 0.62 0.319 0.454 479 422 554 479
1 185 0.0991 0.602 0.31 0.495 549 476 637 543
1 240 0.0754 0.579 0.3 0.556 595 550 746 640
1 300 0.0601 0.562 0.295 0.617 626 591 831 722
1 400 0.047 0.543 0.29 0.681 675 662 920 827
1 500 0.0366 0.525 0.283 0.758 748 744 1043 949
1 630 0.0283 0.507 0.276 0.853 981 856 1180 1076

 

NO. OF  CORES NOMINAL CROSS SECTIONAL AREA MAXIMUM RESISTANCE OF CONDUCTOR AT 20°C OPERATING  INDUCTANCE OPERATING CAPACITY CONTINUOUS CURRENT RATING
In Ground at 20OC In Air at 30OC
- mm2 ohms/km mH/km uF/km Amps Amps
3 50 0.387 0.33 0.3 208 196
3 70 0.268 0.31 0.35 255 249
3 95 0.193 0.29 0.39 307 307
3 120 0.153 0.28 0.43 353 353
3 150 0.124 0.28 0.47 396 406
3 185 0.0991 0.27 0.51 447 464
3 240 0.0754 0.26 0.55 523 548
3 300 0.0601 0.26 0.57 581 632
3 400 0.047 0.26 0.59 653 726

Any questions for us?

For inquiries about our products or price list , please leave your email to us and we will be in touch within 24 hour