BS 6622 19/33(36)kV Medium Voltage Cables Armour XLPE Cable

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

19/33(36)kV Medium Voltage Cables are suitable for power networks,underground and in cable ducting.They can be buried directly

Performance

Voltage rating U0/U(Um):
19/33(36)kV

Test voltage(A.C.):
33kV

Mechanical performance:
-Minimum bending radius of single core:15 x overall diameter
-Minimum bending radius of three cores:12 x overall diameter
-Single core 12 x overall diameter and 3 cores 10 x overall diameter where bends are positioned adjacent to a joint or termination provided that the bending is carefully controlled by the use of a former.

Thermal performance :
-Maximum operating temperature:90℃
-Maximum short-circuit temperature: 250℃(Max.5s)
-Minimum service temperature:-10℃

Fire performance:
-Flame retardant according to IEC/EN 60332-1-2 standard
-Reduced emission of halogens chlorine <15%

Construction

Conductor:
stranded compacted copper or aluminum conductor , class 2.

Conductor Screen:
Semi-conductive conductor screen.

Insulation:
XLPE (cross-linked polyethylene)
-alternative:EPR (Ethylene Propylene Rubber)

Insulation Screen:
Semi-conductive insulation screen.

Metallic Screen:
individual concentric copper wires and/or copper tape.

Filler:
PET(polyethylene terephthalate) fibres

Binding Tape:
polyester tape or non-woven fabric

Optional Inner Sheath:
PVC(Polyvinyl chloride)
-alternative: LSZH (Low Smoke Zero Halogen)

Optional Armour: 
Single-core conductor: AWA (Aluminum Wire Armoring ) or aluminum tape
Three-core conductor: SWA (Steel Wire Armoring ) or galvanized steel tape(single or double layer flat or corrugated)

Outer Sheath:
PVC (polyvinyl chloride)
-alternative :LDPE, MDPE (Low/Medium Density Polyethylene)
-alternative: LSZH (Low Smoke Zero Halogen)

Conductor Shape:
-Single Core:circular, circular compacted
-Three Core:circular, circular compacted, sectorial

Core Identification:
Single Core: Red or black
Three Core: Red , yellow and blue

Sheath Colour:
red, black or other available colour in accord with the request

BS 6622 1933(38)kV Medium Voltage Cables Armour XLPE Cable

19/33(36)kV Three Core Aluminium Conductors XLPE Insulated to BS 6622 Steel Tape Armoured
1.Aluminium Conductor
2.Semi-conductive conductor screen
3.XLPE Insulation
4.Semi-conductive insulation screen
5.Copper tape screen
6.Fillers
7.Tape binder
8.Bedding
9.Galvanised steel tape armour
10. Outer sheath

BS 6622 1933(39)kV Medium Voltage Cables Armour XLPE Cable

19/33(36)kV Three Core Copper Conductors XLPE Insulated to BS 6622 Steel Tape Armoured
1.Copper Conductor
2.Semi-conductive conductor screen
3.XLPE Insulation
4.Semi-conductive insulation screen
5.Copper tape screen
6.Fillers
7.Tape binder
8.Bedding
9.Galvanised steel tape armour
10.Outer sheath

Cable Marking and Packing Materials

Cable Marking:
printing, embossing ,engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Standards

-BS 6622, IEC/EN 60228, IEC 60502-2

BS 6622 Standard 19/33(36)kV Medium Voltage Cables XLPE Cable Physical Performance Parameters

No.of Cores

Nominal Section Area

Minimum Number of Individual Wires in Conductor

Nominal Thickness of  Insulation

Nominal Thickness of Outer Sheath

Nominal Overall Diameter

Nominal Weight

circular

circular compact

sectoral

Cu

Al

Cu

Al

Cu

Al

Cu

Al

-

mm2

-

-

-

-

-

-

mm

mm

mm

kg/km

1

70

19

19

12

12

12

12

8.00

2.00

35.00

1620

1220

1

95

19

19

15

15

15

15

8.00

2.10

37.00

1940

1380

1

120

37

37

18

15

18

15

8.00

2.10

39.00

2240

1510

1

150

37

37

18

15

18

15

8.00

2.20

40.00

2550

1650

1

185

37

37

30

30

30

30

8.00

2.20

42.00

2940

1850

1

240

37

37

34

30

34

30

8.00

2.30

44.00

3580

2120

1

300

61

61

34

30

34

30

8.00

2.40

47.00

4230

2410

1

400

61

61

53

53

53

53

8.00

2.50

50.00

5140

2790

1

500

61

61

53

53

53

53

8.00

2.60

54.00

6270

3250

1

630

91

91

53

53

53

53

8.00

2.70

58.00

7740

3820

1

800

91

91

53

53

-

-

8.00

2.80

62.00

9540

4660

1

1000

91

91

53

53

-

-

8.00

3.00

66.00

11640

5510

3

50

8.00

3.40

79.00

9290

8600

3

70

19

19

12

12

12

12

8.00

3.50

84.00

10390

9340

3

95

19

19

15

15

15

15

8.00

3.60

87.00

11610

10030

3

120

37

37

18

15

18

15

8.00

3.70

91.00

12890

10810

3

150

37

37

18

15

18

15

8.00

3.80

94.00

13980

11380

3

185

37

37

30

30

30

30

8.00

3.90

98.00

15640

12450

3

240

37

37

34

30

34

30

8.00

4.10

104.00

18040

13740

3

300

61

61

34

30

34

30

8.00

4.30

109.00

20480

15250

3

400

61

61

53

53

53

53

8.00

4.50

117.00

24020

16970

Electrical Performance Parameters(copper conductor)

No.of Cores

Nominal Section Area

Max.D.C. Resistance of Conductor at 20℃

   Continuous Current Rating

in ground

in duct

in air

flat

trefoil

flat

trefoil

flat

trefoil

-

mm2

Ω/km

amp

amp

amp

amp

amp

amp

1

70

0.268

270

280

260

270

310

370

1

95

0.193

320

335

305

325

375

460

1

120

0.153

360

380

340

370

430

530

1

150

0.124

410

430

375

410

490

600

1

185

0.0991

455

485

410

460

550

690

1

240

0.0754

520

560

470

540

650

820

1

300

0.0601

580

640

500

610

740

940

1

400

0.047

650

730

530

690

840

1100

1

500

0.0366

710

830

570

780

930

1280

1

630

0.0283

760

940

620

890

1040

1480

1

800

0.0221

810

1060

660

990

1140

1690

1

1000

0.0176

860

1170

690

1090

1230

1900

3

50

0.387

210

210

180

180

220

220

3

70

0.268

250

250

215

215

270

270

3

95

0.193

300

300

255

255

330

330

3

120

0.153

340

340

290

290

380

380

3

150

0.124

380

380

330

330

430

430

3

185

0.0991

430

430

370

370

490

490

3

240

0.0754

500

500

430

430

570

570

3

300

0.0601

540

540

470

470

650

650

Any questions for us?

For inquiries about our products or price list , please leave your email to us and we will be in touch within 24 hour