ASTM 25kV Overhead Space Aerial Cable AAAC 3-layer Track-resistant PE

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

Power is often delivered to the user's service head, when connection to the service entry is made, using a 25kV overhead space aerial cable.
To be used with conductor temperatures no more than 75°C for polyethyl insulated conductors and 90°C for crosslinked conductors at 600V or less phase to phase.

Constructions

Single cable with an AAAC conductor, a 3-layer extruded shield and covering system, consisting of an extruded semiconducting thermoplastic conductor shield, and a 2-layer covering.
The covering inner layer is a low-, medium- or high-density polyethylene (LDPE, MDPE or HDPE), while the outer layer is track-resistant medium- or high-density polyethylene (TK-MDPE or TK-HDPE).
All layers are bonded together.

Conductor:
AAAC

Conductor Shield:
Extruded semiconducting thermoplastic shield which is free stripping from the conductor and bonded to the covering.

Inner and Outer Covering:
2-layer low-, medium- or high-density polyethylene covering (LDPE, MDPE or HDPE), where the outer layer is track-resistant (TK-MDPE or TK-HDPE). All layers are bonded together. The outer layer shall be black or gray, sunlight resistant and track resistant.

ASTM 25kV Space Aerial Cable SAC Overhead Power Cables ACSR 3-layer Track-resistant XLPE (2)

Standards

These cables are manufactured and tested to meet or exceed the following standards:
ASTM B230 – Aluminum 1350–H19 Wire for Electrical Purposes
ASTM B231 – Concentric-Lay-Stranded Aluminum 1350 Conductors
ASTM B400 – Compact Round Concentric-Lay-Stranded Conductors
ASTM D1248 – Polyethylene Plastics Extrusion Materials for Wire and Cable
ICEA S-121-733 – Tree Wire and Messenger Supported Spacer Cable 

ASTM Standard 25kV Overhead Aerial Cable AAAC PE

Conductor
Size
Equivalent
AAC
Conductor
Stranding
Conductor
Diameter
Conductor
Shield
Thickness
Covering
Thickness
Inner
Layer
Covering
Thickness
Outer
Layer
Overall
Diameter
Weight
Conductor
Weight
Net
Rated
Strength
AWG
or
kcmil
AWG
or
kcmil
No. in in in in in lb/FT lb/FT lb/FT
48.69 4 7 0.25 0.015 0.075 0.075 0.58 45.4 139 1760
77.47 2 7 0.316 0.015 0.075 0.075 0.646 72.24 181 2800
123.3 1/0 7 0.398 0.015 0.075 0.075 0.728 114.9 242 4270
155.4 2/0 7 0.447 0.015 0.075 0.075 0.777 144.9 284 5390
195.7 3/0 7 0.502 0.015 0.075 0.075 0.832 182.5 334 6790
246.9 4/0 7 0.563 0.015 0.075 0.075 0.893 230.2 395 8560
312.8 266.8 19 0.642 0.015 0.075 0.075 0.972 291.6 474 10500
394.5 336.4 19 0.721 0.015 0.075 0.075 1.051 367.9 569 13300
465.4 397.5 19 0.783 0.015 0.075 0.075 1.113 433.9 649 15600
559.5 477 19 0.858 0.02 0.075 0.075 1.198 521.7 762 18800
652.4 556.5 19 0.927 0.02 0.08 0.08 1.287 608.3 882 21900
740.8 636 37 0.991 0.02 0.08 0.08 1.351 690.8 980 24400

Any questions for us?