BS EN 50397 MVCC/MVC Medium Voltage Covered Conductors For Overhead Lines

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Quick Details

BS EN 50397-1:2020 Covered conductors for overhead lines and the related accessories for rated voltages above 1 kV AC and not exceeding 36 kV AC Covered conductors

Application

Medium voltage covered conductors are Used for primary and secondary overhead distribution where limited space is available or desired for rights-of-way. Installed the same as bare conductors, however, covering is effective in preventing direct shorts and instantaneous flash overs should tree limbs or other objects contact conductors in such close proximity.

Tree Wire
Used for spans where trees crowd the right-of-way, such as in wooded residential areas, when a minimum of interference with the environment is desired. Covering minimizes power outages due to conductor contact with tree limbs, reducing the need for frequent or severe trimming.

Covered Aerial MV Cable
Installed with other Covered Aerial MV cables and a supporting messenger through a series of space- maintaining devices (spacers). The resulting close-proximity configuration minimizes the amount of space and hardware required for line installation, particularly useful in congested areas.

Spacer Cable
Installed with other spacer cables and a supporting messenger through a series of space- maintaining devices(spacers). The resulting close-proximity configuration minimizes the amount of space and hardware required for line installation ;particularly useful in congested areas.

Construction

AAC (1350-H19), AAAC or ACSR conductors, concentrically stranded. Available with black or gray track-resistant, high-density polyethylene (HD) or black track-resistant cross linked polyethylene (XLP) covering.

Conductor:
Longitudinally water tight stranded all aluminium alloy (AAAC) or aluminium conductor steel reinforced (ACSR).

A (conductor screen):
Water swellable semi-conducting tape (if required) and extruded semi-conducting compound.

B (inner insulation):
XLPE

C (outer insulation):
UV protected and anti-tracking black colored XLPE or HDPE.

BS-EN-50397-(2)

Cable Marking and Packing Materials

Cable Marking:
printing, embossing, engraving

Packaging:
wooden drum, steel drum, steel-wooden drum

Anti tracking properties

Anti-tracking property is must for MVCC outer XLPE/HDPE. As per the experience of several international utilities, in the absence of anti-tracking, XLPE or HDPE, MVCC fails within a short time period of 5-6 months. Anti-tracking jacketing has been specially designed to meet the outdoor conditions and performance requirements of 13.8 KV to 34.5 KV distribution networks. The material has an excellent resistance to arc, corrosion inhibitor, fungicide activity, oil resistance, and weather conditions like humidity, pollution, presence of salt in atmosphere etc. There is a special test method for carrying out the tests for the anti-tracking in BS EN 50397-1.

Applicable Standards

BS EN 50397-1, BS EN 50182, IS 398-2, IS 398-4, IEC 61089

BS EN 50397 MVCC/MVC Medium Voltage Covered Conductors For Overhead Lines

15kv Overhead Covered Conductor

Cross section

No. of wires

Conductor dia.

Overall Diameter

Minimum breaking load

Approx. weight

Max. DC-resistance at 20°C

Ampacity 90°C

[mm²]

[mm]

[mm]

[kgf]

[kg/km]

[Ohm/km]

[A]

35

7

7.1

13.6

464

190

0.868

187

50

7

8.2

14.7

663

235

0.641

225

70

19

9.7

16.2

928

315

0.443

282

95

19

11.5

18

1259

400

0.32

345

120

19

12.9

19.4

1591

500

0.253

401

150

19

14.2

20.7

1988

580

0.206

456

185

37

16.2

22.6

2452

695

0.164

525

240

37

18.4

24.9

3182

875

0.125

625

300

37

20.7

27.1

3977

1070

0.1

721

25kv Overhead Covered Conductor

Cross section

No. of wires

Conductor dia.

Overall Diameter

Minimum breaking load

Approx. weight

Max. DC-resistance at 20°C

Ampacity 90°C

[mm²]

[mm]

[mm]

[kgf]

[kg/km]

[Ohm/km]

[A]

35

7

7.1

15.7

464

235

0.868

186

50

7

8.2

16.8

663

305

0.641

224

70

19

9.7

18.3

928

370

0.443

280

95

19

11.5

20.1

1259

460

0.32

343

120

19

12.9

21.5

1591

560

0.253

397

150

19

14.2

22.8

1988

650

0.206

450

185

37

16.2

24.8

2452

770

0.164

519

240

37

18.4

27

3182

960

0.125

617

300

37

20.7

29.3

3977

1155

0.1

712

35kv Overhead Covered Conductor

Cross section

No. of wires

Conductor dia.

Overall Diameter

Minimum breaking load

Approx. weight

Max. DC-resistance at 20°C

Ampacity 90°C

[mm²]

[mm]

[mm]

[kgf]

[kg/km]

[Ohm/km]

[A]

70

19

9.7

25.7

928

620

0.443

270

95

19

11.5

27.5

1259

732

0.32

329

120

19

12.9

28.9

1591

830

0.253

381

150

19

14.2

30.2

1988

937

0.206

432

185

37

16.2

32.2

2452

1083

0.164

497

240

37

18.4

34.4

3182

1290

0.125

589

300

37

20.7

36.7

3977

1502

0.1

674