SANS 1507, NRS 063 & NRS 017 Airdac SNE Cable 600/1000V

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

Seperate Neutral & Earth SNE Cable is used for house connections. This Airdac SNE cable can only be used for single phase supply. Cable is made to be suspended in the air. Aerial SNE Cable is also suitable for underground general use, sub main distribution boxes, street lighting systems and high rise buildings. Split concentric cable suitable for power distribution as an underground or overhead cable.

Performance

Electrical performance U0/U:
600/1000V

Chemical performance:
chemical, UV&oil resistance

Mechanical performance:
minimum bending radius:10 x overall diameter

Terminal performance:
-Maximum service temperature:90℃
-Maximum short-circuit temperature: 250℃(Max.5s)
-Minimum service temperature:-40℃

Fire performance:
-Flame retardant according to IEC/EN 60332-1 standard

Construction

Phase Conductor:
Class 2 Hard Drawn Copper Conductor

Insulation:
LV-XLPE (Cross-linked polyethylene)

Earth Conductor:
Solid Copper Wire

Phase Color Code:
Red, Black & Bare Copper

Ripcord:
Nylon

Binder Tape:
Polyester Tape

Outer Sheath:
XLPE/PVC/PE (Polyethylene)

SANS-1507,-NRS-063-&-NRS-017-Airdac-SNE-cable-600-1000V-(2)

1.Insulation
2.Phase Conductor
3.Insulation
4.Neutral Conductor
5.Ripcord

6.Binder Tape
7.Outer Sheath
8.Pilot Core
9.Earth Conductor

Cable Marking and Packing Materials

Packing Materials:
printing, embossing, engraving

Packaging:
wooden drum, steel drum, steel-wooden drum

Specifications

-SANS 1507, NRS 063 & NRS 017 Standard

AIRDAC CABLE SPECIFICATION AND PHYSICAL PERFORMANCE

Phase Conductor Area Size 4 6 10 16 mm2
Neutral Conductor Area Size 4 6 10 16 mm2
Earth Conductor Wires (No. X dia.) 3/1.35 3/1.38 3/1.78 3/2.20 mm
Phase Conductor Diam. 3.8 4.3 5.1 6.2 mm2
Pilot Cores dia. or Dummy Fillers 1.2 1.2 1.2 1.2 mm
Overall Diameter 6.5 7.1 8.7 10.6 mm2
Cable Mass 158 204 325 435 kg/km

ELECTRICAL PERFORMANCE

Phase Conductor Resistance (DC Resistance @ 20°C) 4.61 3.08 1.83 1.15 Q/km
Phase Conductor Resistance (AC Resistance @ 90°C) 5.4 3.6 2.1 1.47 Q/km
Phase Conductor Impedance (Z) 5.49 3.7 2.19 1.39 Q/km
Current ⑴ in Air @ 30°C 30 40 50 70 A

Any questions for us?

For inquiries about our products or price list , please leave your email to us and we will be in touch within 24 hour