AS/NZS 3560.1 0.6/1kV Low Voltage Aerial Bundled Cable AL XLPE/PE

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

The AS/NZS 3560.1 standard Low Voltage Aerial Bundled Cable is in temporary power distribution to street lighting and secondary pole-pole service cables. ABC Aerial Bundled Cable feature light-stranded aluminium conductors, both single-core and multi-core, covered with XLPE/PE/PVC insulation. They are commonly used in temporary power installations such as on-base buildings.

Performance

Electrical performance:
0.6/1kV

Chemical performance:
chemical, UV&oil resistance

Terminal performance:
maximum service temperature: 90℃; maximum short-circuit temperature: 250℃(max.5s); minimum service temperature:-40℃

Construction

Concentric strands or compact aluminum conductor, polyethylene or crosslinked polyethylene insulation.

Phase conductor:
circular stranded, rounded, compact aluminum conductor

Phase Core Identification:
colour strip, rib or number

Neutral/Messenger conductor:
circular stranded, rounded, compact aluminum conductor

Insulation:
black polyethylene(PE) or crosslinked polyethylene(XLPE)

ASNZS 3560.1 0.61kV Low Voltage Aerial Bundled Cable AL XLPEPE (2)

1. Conductor

2. Insulation

Cable Marking and Packing Materials

Cable Marking:
printing, embossing, engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Specifications

- AS/NZS 3560.1 standard low voltage ABC Cable

AS/NZS 3560.1 Standard Low Voltage Aerial Bundled Cable Specs Physical Performance Parameters

Nominal Section Area

Nominal Diameter of Conductor

Nominal Thickness of Insulation

Nominal Diameter of Insulation

Nominal Diameter Over Laid-up Cores

Nominal Linear Mass

mm2

mm

mm

mm

mm

kg/km

2 cores

16

4.7

1.3

7.4

14.8

130

25

5.9

1.3

8.6

17.2

190

35

6.9

1.3

9.6

19.3

250

50

8.1

1.5

11.2

22.3

340

95

11.4

1.7

14.9

29.8

640

3 cores

25

5.9

1.3

8.6

18.5

290

35

6.9

1.3

9.6

20.8

370

50

8.1

1.5

11.2

24.1

510

4 cores

16

4.7

1.3

7.4

17.8

270

25

5.9

1.3

8.6

20.8

390

35

6.9

1.3

9.6

23.2

500

50

8.1

1.5

11.2

27.0

670

70

9.7

1.5

12.8

30.8

930

95

11.4

1.7

14.9

36.0

1280

120

12.8

1.7

16.3

39.3

1570

150

14.2

1.7

17.7

42.8

1890

Mechanical Performance Parameters

Nominal Section Area

Min.Bending Radius

Rec. Tension

Min.Breaking Load of Cable

Modulus of Elasticity

Coefficient of Linear Expansion

Single

Core

Complete cable

Highest Tension Everyday

Max. Working Tension

mm2

mm

mm

kN

kN

kN

GPa

x 10–6/°C

2 cores

16

30

90

0.79

1.23

4.4

59

23.0

25

35

100

1.26

1.96

7.0

59

23.0

35

60

120

1.76

2.74

9.8

59

23.0

50

65

130

2.52

3.92

14.0

59

23.0

95

90

270

4.79

7.45

26.6

59

23.0

3 cores

25

35

110

1.89

2.94

10.5

59

23.0

35

60

120

2.65

4.12

14.7

59

23.0

50

65

140

3.78

5.88

21.0

59

23.0

4 cores

16

30

110

1.58

2.46

8.8

59

23.0

25

35

120

2.52

3.92

14.0

59

23.0

35

60

140

3.53

5.49

19.6

59

23.0

50

65

160

5.04

7.84

28.0

59

23.0

70

75

280

7.06

11.0

39.2

56

23.0

95

90

320

9.58

14.9

53.2

56

23.0

120

100

350

12.1

18.8

67.2

56

23.0

150

110

390

15.1

23.5

84.0

56

23.0

Electrical Performance Parameters

Nominal

Section Area

D.C.Resistance at 20°C

A.C.Resistance. at 50Hz 80°C

Inductive reactance at 50Hz

Voltage Drop at 50Hz  80°C

Continuous Current Carrying Capacity

Fault Current Rating

for 1s

still air

1s/m wind

2s/m wind

mm2-

Ω/km

Ω/km

Ω/km

mV/A.m

A

A

A

kA

2 cores

16

1.91

2.37

0.094

4.75

49

78

91

1.4

25

1.20

1.49

0.089

2.99

64

105

120

2.2

35

0.868

1.08

0.086

2.16

78

125

145

3.1

50

0.641

0.796

0.086

1.60

94

150

180

4.1

95

0.320

0.398

0.080

0.812

140

230

275

8.3

3 cores

25

1.20

1.49

0.089

2.99

59

97

115

2.2

35

0.868

1.08

0.086

2.16

72

120

135

3.1

50

0.641

0.796

0.086

1.60

88

140

165

4.1

4 cores

16

1.91

2.37

0.10

4.11

44

74

86

1.4

25

1.20

1.49

0.097

2.59

59

97

115

2.2

35

0.868

1.08

0.094

1.87

72

120

135

3.1

50

0.641

0.796

0.093

1.39

88

140

165

4.1

70

0.443

0.551

0.088

0.966

110

175

205

6.0

95

0.320

0.398

0.087

0.706

135

215

255

8.3

120

0.253

0.315

0.085

0.566

155

250

300

10.5

150

0.206

0.257

0.084

0.468

180

280

345

12.9

Note:
Voltage drops are single-phase for 2 & 3 core cables and three-phase for 4 core cables.
Continuous current ratings are based on an ambient temperature of 40°C, maximum conductor temperature of 80°C and solar radiation intensity of 1000W/m2. Ratings for 2 & 3 core cables are based on all cores fully loaded. Ratings for 4 core cables are based on a lightly loaded neutral. Fault current ratings are based on initial and final conductor temperatures of 80°C and 210°C respectively.