AS/NZS 5000.1 0.6/1kV Unarmored Orange Circular Cable XLPE Multicore Cable

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

0.6/1kV Unarmored XLPE Multicore Cable is used in mains, sub-mains and sub-circuits that are not enclosed, enclosed in conduits, directly buried or in underground ducts, and are used in buildings and factories where they are not subject to mechanical damage.

Performance

Electrical performance U0/U:
0.6/1kV

Chemical performance:
chemical, UV&oil resistance

Mechanical performance:
minimum bending radius:15 x overall diameter

Terminal performance:
-Maximum service temperature: 90℃
-Maximum short-circuit temperature: 250℃(Max.5s)
-Minimum service temperature: -10℃

Construction

Conductor:
Plain annealed copper

Insulation:
XLPE (cross-linked polyethylene)

Outer Sheath:
Polyvinyl chloride compound PVC 5V-90

Core Identification:
2C + E - Red, Black, Green/yellow
3C + E – Red, White, Blue, Green/yellow
4C + E - Red, White, Blue, black, Green/yellow

Sheath Colour:
Orange

1kV-Multicore-XLPE-Insulated-PVC-Sheathed-Unarmored-Cabl-(

1. Conductor
2. XLPE Insulated

3. PVC Sheath

Cable Marking and Packing Materials

Cable Marking:
printing, embossing ,engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Specifications

-AS/NZS 5000.1, AS/NZS 3008, AS/NZS 1125, SAA-173128-EA

AS/NZS 5000.1 0.6/1kV 2C+E XLPE Insulated PVC Sheathed Unarmored Cables Specification

NOM. CONDUCTOR AREA CONDUCTOR NOM. INSULATION THICKNESS NOM. EARTH CONDUCTOR AREA NOM. EARTH CONDUCTOR INSULATION THICKNESS NOM. SHEATH THICKNESS NOM. OVERALL DIAMETER APPROX. MASS
MM2 NO./ OD MM MM2 MM MM MM KG/KM
10 7/1.35 0.7 4 0.7 1.4 14.9 380
16 7/1.70 0.7 6 0.7 1.4 16.6 520
25 7/2.14 0.9 6 0.7 1.4 20.2 750
35 7/2.65 0.9 10 0.7 1.4 23 985
50 19/1.89 1 16 0.7 1.4 24.1 1310
70 19/2.24 1.1 25 0.9 1.4 29.8 1860
95 19/2.65 1.1 25 0.9 1.5 31.6 2415
120 19/2.94 1.2 35 0.9 1.6 35.5 3055

AS/NZS 5000.1 0.6/1kV 2C+E XLPE Insulated PVC Sheathed Unarmored Cables Electrical Performance

CONDUCTOR CURRENT RATINGS ELECTRICAL CHARACTERISTICS
NOMINAL AREA UNENCLOSED  IN AIR BURIED DIRECT BURIED IN DUCTS MAXIMUM DC RESISTANCE @20°C MAXIMUM AC RESISTANCE @90℃ REACTANCE THREE PHASE VOLTAGE DROP @90℃
MM2 A  A A OHM/KM OHM/KM OHM/KM MV/AM
10 80 107 82 1.83 2.33 0.084 1.68
16 107 139 107 1.51 1.47 0.081 2.95
25 143 182 139 0.727 0.927 0.081 1.86
35 160 130 160 0.524 0.669 0.0786 1.35
50 195 160 190 0.387 0.494 0.0751 1
70 250 200 235 0.268 0.343 0.0741 0.703
95 310 240 285 0.193 0.248 0.0725 0.52
120 360 285 325 0.153 0.197 0.0713 0.423

AS/NZS 5000.1 0.6/1kV 3C+E XLPE Insulated PVC Sheathed Unarmored Cables Specification

NOM. CONDUCTOR AREA CONDUCTOR NOM. INSULATION THICKNESS NOM. EARTH CONDUCTOR AREA NOM. EARTH CONDUCTOR INSULATION THICKNESS NOM. SHEATH THICKNESS NOM. OVERALL DIAMETER APPROX. MASS
MM2 NO./ OD MM MM2 MM MM MM KG/KM
10 7/1.35 0.7 4 0.7 1.4 16 475
16 7/1.70 0.7 6 0.7 1.4 18.3 690
25 7/2.14 0.9 6 0.7 1.4 21.8 1020
35 7/2.65 0.9 10 0.7 1.4 26.9 1400
50 19/1.89 1 16 0.7 1.4 30.7 1900
70 19/2.24 1.1 25 0.9 1.4 35.9 2600
95 19/2.65 1.1 25 0.9 1.5 38 3050
120 19/2.94 1.2 35 0.9 1.6 41.8 4200
150 19/3.28 1.4 50 1 1.7 43 5250
185 37/2.65 1.6 70 1.1 1.8 48.4 6620
240 37/2.94 1.7 95 1.1 2 54.5 8720

AS/NZS 5000.1 0.6/1kV 3C+E XLPE Insulated PVC Sheathed Unarmored Cables Electrical Performance

CONDUCTOR CURRENT RATINGS ELECTRICAL CHARACTERISTICS
NOMINAL AREA UNENCLOSED  IN AIR BURIED DIRECT BURIED IN DUCTS MAXIMUM DC RESISTANCE @20°C MAXIMUM AC RESISTANCE @90℃ REACTANCE THREE PHASE VOLTAGE DROP @90℃
MM2 A  A A OHM/KM OHM/KM OHM/KM MV/AM
10 68 91 68 1.83 2.33 0.084 4.05
16 91 118 89 1.15 1.47 0.081 2.55
25 121 155 118 0.727 0.927 0.081 1.61
35 149 182 144 0.524 0.669 0.079 1.17
50 187 219 171 0.387 0.494 0.075 0.868
70 237 268 214 0.268 0.343 0.074 0.609
95 292 321 257 0.193 0.248 0.073 0.45
120 305 250 275 0.153 0.197 0.0713 0.366
150 350 280 310 0.124 0.16 0.0718 0.307
185 405 325 355 0.0991 0.129 0.072 0.259
240 480 385 420 0.0754 0.0998 0.0709 0.216

AS/NZS 5000.1 0.6/1kV 4C+E XLPE Insulated PVC Sheathed Unarmored Cables Specification

NOM. CONDUCTOR AREA CONDUCTOR NOM. INSULATION THICKNESS NOM. EARTH CONDUCTOR AREA NOM. EARTH CONDUCTOR INSULATION THICKNESS NOM. SHEATH THICKNESS NOM. OVERALL DIAMETER APPROX. MASS
MM2 NO./ OD MM MM2 MM MM MM KG/KM
10 7/1.35 0.7 4 0.7 1.4 16 475
16 7/1.70 0.7 6 0.7 1.4 18.3 690
25 7/2.14 0.9 6 0.7 1.4 21.8 1020
35 7/2.65 0.9 10 0.7 1.4 26.9 1400
50 19/1.89 1 16 0.7 1.4 30.7 1900
70 19/2.24 1.1 25 0.9 1.4 35.9 2600
95 19/2.65 1.1 25 0.9 1.5 38 3050
120 19/2.94 1.2 35 0.9 1.6 41.8 4200
150 19/3.28 1.4 50 1 1.7 43 5250
185 37/2.65 1.6 70 1.1 1.8 48.4 6620
240 37/2.94 1.7 95 1.1 2 54.5 8720

AS/NZS 5000.1 0.6/1kV 4C+E XLPE Insulated PVC Sheathed Unarmored Cables Electrical Performance

CONDUCTOR CURRENT RATINGS ELECTRICAL CHARACTERISTICS
NOMINAL AREA UNENCLOSED  IN AIR BURIED DIRECT BURIED IN DUCTS MAXIMUM DC RESISTANCE @20°C MAXIMUM AC RESISTANCE @90℃ REACTANCE THREE PHASE VOLTAGE DROP @90℃
MM2 A  A A OHM/KM OHM/KM OHM/KM MV/AM
10 68 91 68 1.83 2.33 0.084 4.05
16 91 118 89 1.15 1.47 0.081 2.55
25 121 155 118 0.727 0.927 0.081 1.61
35 149 182 144 0.524 0.669 0.079 1.17
50 187 219 171 0.387 0.494 0.075 0.868
70 237 268 214 0.268 0.343 0.074 0.609
95 292 321 257 0.193 0.248 0.073 0.45
120 305 250 275 0.153 0.197 0.0713 0.366
150 350 280 310 0.124 0.16 0.0718 0.307
185 405 325 355 0.0991 0.129 0.072 0.259
240 480 385 420 0.0754 0.0998 0.0709 0.216