AEIC CS8 5-35kV Al Conductor AIA Cable Aluminum Interlocked Armor

DOWNLOAD CATEGORY SPECIFICATIONS

Product Details

Product parameter

Application

An affordable, tough, and trustworthy alternative to labor-intensive cable in conduit wiring techniques is provided by Al Conductor AIA Cable Aluminum Interlocked Armor.
installed on supports that are no more than six feet apart, such as metal racks, troughs, raceways, cable trays, or brackets.
installed in wet or dry settings, wet or dry work, immediately buried or embedded in concrete, and exposed or concealed work.

Construction

Conductor:
A or B class ASTM B 231-compliant compressed concentric stranded aluminum alloy 1350. With conductor filling compound, stranded conductors are water-blocked.

Conductor Shield:
Insulation-bonding thermosetting extruded semiconducting cover that is free peeling from the conductor.

Insulation:
Tree-Retardant Cross-Linked Polyethylene (TRXLPE), as described in ANSI/ICEA S-94-649, is an extruded, unfilled material.

Insulation Shield:
Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.

Metallic Shield:
The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap.

Ground Wire:
Three bare copper ground wires placed at the interstice of the conductor.

Fillers:
Non hygroscopic fillers, forming a firm and cylindrical cable core.

Binder Tape:
A binder tape is applied to maintain core symmetry and mechanical stability.

Armor:
Aluminum Interlocked Armor applied over the binder tape of the cable core

Jacket:
Black, sunlight resistant, flame retardant PVC jacket

AEIC CS8 5-35kV Al Conductor AIA Cable Aluminum Interlocked Armor (2)

1.Conductor
2.Conductor Shield
3.Insulation
4.Insulation Shield
5.Copper Tape Shied

6.Ground Conductor
7.Filler
8.Binder
9.AIA Armour
10.Overall Jacket

Cable Marking and Packing Materials

Cable Marking:
printing, embossing ,engraving

Packing Materials:
wooden drum, steel drum, steel-wooden drum

Specifications

- AEIC CS8, Specifications for Shielded Power Cable, 5-46kV
- ICEA S-93-639, 5-46 kV Shielded Power Cable
- ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
- UL-1072 MV-105

- UL-1569, Metal Clad Cables
- IEEE 383 Flame Test
- For 105°C continuous, 140°C emergency, 250°C short-circuit operation.
- UL MC-HL available upon request

AEIC CS8 5-35kV Al Conductor AIA Cable Specification

Size Insulation
Thickness
Ground
Wires
Size of
Ground
Wires
Conductor
Diameter
Insulation
Diameter
Insulation
Shield
Diameter
Overall
Jacket
Diameter
Approximate
Weight
Minimum
Bending
Radius
Ampacity
105ºC
in
Duct
Ampacity
105ºC
in
Air
AWG / KCMIL (mil) No. AWG in in in in lb/MFT in - -
4 90 3 10 0.215 0.45 0.51 1.47 1001 11 86 90
2 90 3 10 0.266 0.5 0.56 1.58 1165 12 110 120
1 90 3 10 0.299 0.53 0.59 1.68 1298 12 130 140
1/0 90 3 10 0.336 0.57 0.63 1.75 1431 13 150 160
2/0 90 3 8 0.379 0.61 0.67 1.87 1698 14 170 185
3/0 90 3 8 0.423 0.66 0.71 1.96 1887 14 195 215
4/0 90 3 8 0.479 0.71 0.77 2.08 2121 15 220 250
250 90 3 8 0.522 0.76 0.82 2.19 2338 16 245 280
350 90 3 7 0.622 0.86 0.92 2.44 2927 18 310 345
500 90 3 6 0.742 0.98 1.05 2.73 3734 20 365 430
750 90 3 5 0.917 1.16 1.24 3.14 4987 23 460 550
1000 90 3 4 1.071 1.32 1.39 3.48 6177 25 535 650